t_DHWHP_max
241 (PLC: 40242)
242 (PLC: 40243)
t_DHWHP_restrict
243 (PLC: 40244)
T4autocmin
T4autohmax
244 (PLC: 40245)
T1S_H. A_H
245 (PLC: 40246)
T5S_H. A_DHW
246 (PLC: 40247)
247 (PLC: 40248)
ECO parameter
248 (PLC: 40249)
ECO parameter
249 (PLC: 40250)
ECO parameter
250 (P LC:40251)
ECO parameter
251 (PLC: 40252)
Comfort parameter
252 (P LC:40253)
Comfort parameter
253 (PLC: 40254)
Comfort parameter
254 (P LC:40255)
Comfort parameter
255 (PLC: 40256)
t_DRYUP
256 (PLC: 40257)
t_HIGHPEAK
t_DRYD
257 (PLC: 40258)
T_DRYPEAK
258 (PLC: 40259)
t_firstFH
259 (PLC: 40260)
T1S (first floor heating)
260 (PLC: 40261)
Longest duration of water heating by the heat pump, range:
10~600 min, default setting: 120 min;
Duration of limited water heating by the heat pump, range:
10~600 min, default setting: 30 min;
Default setting: 25°C, range: 20~29°C, setting interval: 1°C
Default setting: 17°C, range: 10~17°C, setting interval: 1°C
In the holiday mode, setting of T1 in the heating mode, range:
20~25°C, default setting: 25°C
In the holiday mode, setting of T1 in the water heating mode,
range: 20~25°C, default setting: 25°C
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Temperature rise day number, range: 4~15 days, default setting: 8 days
Drying day number, range: 3~7 days, default setting: 5 days
Temperature drop day number, range: 4~15 days, default setting: 5 days
Highest drying temperature, range: 30~55°C, default setting: 45°C
Running time of floor heating for the first time, default setting: 72 hrs,
range: 48-96 hrs
T1S of floor heating for the first time, range: 25~35°C, default setting: 25°C