Setting the mode
1 (PLC:40002)
2 (PLC:40003)
Setting water temperature T1s
Setting air temperature Ts
3 (PLC:40004)
4 (PLC:40005)
T5s
5 (PLC:40006)
Function setting
6 (PLC:40007)
Curve selection
7 (PLC:40008)
Forced water heating
8 (PLC:40009)
Forced TBH
Forced IBH1
9 (PLC:40010)
10 (PLC:40011)
In cooling mode,T1S low temp setting range is 5~25°C;T1S high temp setting range is 18~25°C.
In heating mode,T1S low temp setting range is 22~55°C;T1S high temp setting range is 35~60°C.
1: Auto; 2: Cool; 3: Heat;
Water temperature T1s is corresponding to the floor heating.
The room temperature range is between 17°C and 30°C, and is
valid when there is Ta.
The water tank temperature range is between 40°C and 60°C.
BIT15
Reserved
BIT14
Reserved
BIT13
Reserved
BIT12
1: curve setting is enabled; 0: curve setting is disabled.
BIT11
DHW pump's running constant-temperature water recycling
BIT10
ECO mode
BIT9
Reserved
BIT8
Holiday home (the status can only be read, not changed)
BIT7
0: Silent mode level1; 1: Silent mode level2
BIT6:
Silent mode
Holiday away (the status can only be read, but cannot be
BIT5:
changed)
BIT4:
Disinfect
BIT3:
Reserved
BIT2:
Reserved
BIT1:
Reserved
BIT0:
Reserved
Curve 1-8
TBH is the electric water tank heater.
IBH1 and 2 are the hydraulic module's rear
0: Invalid
electric heater.
1: Forced on
IBH1 and 2 can be activated together.
2: Forced off
TBH cannot be activated together with IBH1
and 2.
0-24 Hours
44
Others: Invalid