Parameter setting 2
211 (PLC:40212)
dT5_On
212 (PLC: 40213)
dT1S5
213 (PLC: 40214)
T_Interval_DHW
214 (PLC: 40215)
T4DHWmax
215 (PLC: 40216)
216 (PLC: 40217)
T4DHWmin
217 (PLC: 40218)
t_TBH_delay
dT5_TBH_off
218 (PLC: 40219)
T4_TBH_on
219 (PLC: 40220)
T5s_ DI
220 (PLC: 40221)
BIT15
Reserved
Reserved
BIT14
BIT13
Reserved
Reserved
BIT12
Reserved
BIT11
Reserved
BIT10
BIT9
Reserved
Define the port,
BIT8
0=remote ON/OFF; 1=DHW heater
BIT7
Smart grid, 0=NON; 1=YES
BIT6:
Enable or disable the Tw2, 0=NON ; 1=YES
Setting the high/low temperature of cooling
BIT5:
mode T1S
Setting the high/low temperature of heating
BIT4:
mode T1S
BIT3:
Double zone setting is valid
BIT2:
Reserved
BIT1:
Reserved
BIT0:
Reserved
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 10°C, range: 5~40°C, setting interval: 1°C
Default setting: 5 min, range: 5~30 min, setting interval: 1 min
Default setting: 43°C, range: 35~43°C, setting interval: 1°C
Default setting: -10°C, range: -25~5°C, setting interval: 1°C
Default setting: 30 min, range: 0~240 min, setting interval: 5 min
Default setting: 5°C, range: 0~10°C, setting interval: 1°C
Default setting: 5°C, range: -5~20°C, setting interval: 1°C
Temperature of the disinfection water tank, range: 60~70°C, default setting: 65°C