3.3 HYDRAULIC SYSTEMS
WARNING:
It is necessary to install a filter on the fuel supply line.
The pump is designed to allow working with two pipes. In order to obtain one pipe working it
is necessary to unscrew the return plug (2), remove the by-pass screw (3) and then screw
again the plug (2), (see fig. 7).
Before starting the burner make sure that the return pipe-line is not clogged. An excessive
back pressure would cause the damage of the pump seal.
CRONO 10-L2, 15-L2 and 20-L2
Fig. 7
S7688
1 - Suction line
2 - Return line
3 - By-pass screw
4 - Gauge connection
5 - 2 nd stage pressure adjuster
6 - Suction gauge connection
7 - 1 st stage pressure adjuster
8 - 2 nd stage valve
9 - 1st stage valve
10 - Auxiliary pressure test point
2701
CRONO 25-L2
9
10
1 - Suction line
2 - Return line
3 - By-pass screw
4 - Gauge connection
5 - 2 nd stage pressure adjuster
6 - Suction gauge connection
7 - 1 st stage valve
8 - Valve casing assembly
9 - 2 nd stage valve
10 - Auxiliary pressure test point
5
GB
4
Fig. 7
8
7
1
D5405
6
5
4
3
2