Jumper 27
Move jumper 27 position
In standard, ESD control is a close command. Jumper 28 position
CLOSE.
Jumper 28
Move jumper 28 to position OPEN for open command.
In standard, ESD control does not override the motor thermal
sensor
Switch 8
Move switch 8 to position B to by-pass the motor thermal sensor
when ESD control.
- Configuration of ESD control: jumpers 27 and 28
6.6 LOCAL CONTROL INHIBITION
The inhibition of the local control is a remote command. This command freezes open and close
commands sent in local and authorise remote commands even if the local / remote selector is in local position.
In standard configuration, local stop and general stop remain possible locally on the actuator.
4
5
6
7
8
9
10
11
12
For inhibition of local stop and general stop, see 6.3 (switch 4 on position B).
Note: the command inhibition of local control is not available with the option positioner.
It is replaced [automatically] by the function AUTO / ON-OFF CONTROL.
to have ESD by opening a contact.
Caution : In this configuration,
if ESD input is not connected,
the actuator receives an ESD
operation command as soon
as powered on. If no ESD wire
is available at the start-up
stage, it is recommended to
add a jumper at the wiring
terminal strip (in place of ESD
wire) prior to power on.
- By-pass of motor thermal sensor
when ESD control.