UK | 6 Settings main menu
Unit filter
Parameter
Filter service life
unit filter
Filter change
unit filter
The filter service life of the unit filter is dis-
played (corresponds to service life of supply
air fan). Once the set timer interval has
elapsed, a filter change message appears.
If the filter is changed prematurely, the
filter change must be confirmed. This is done
by selecting "yes" under Filter change, unit
filter. The filter service life is reset.
External filter
Parameter
External filter
Filter service life
external filter
Filter change
external filter
External filter "yes" activates the filter change
display for an outside air filter upstream of the
ventilation unit (brine earth heat exchanger).
If the filter is changed prematurely, the
filter change must be confirmed. This is done
by selecting "yes" under Filter change, exter-
nal filter. The filter service life is reset.
66
Setting
3 to 12 months
no / yes
Setting
no / yes
3 ... 6 ... 18 months
no / yes
Room filter
Parameter
Room filter
Filter service life
room filter
Filter change
room filter
Room filter "yes" activates the filter change
display for the room filters in the air inlets, e.g.
for exhaust air filter elements.
If the filter is changed prematurely, the
filter change must be confirmed. This is done
by selecting "yes" under Filter change, room
filter. The filter service life is reset.
Duration of ventilation level
Parameter
Duration of ventilation
level
Operating time of a manually selected
ventilation level in Auto Sensor or Auto Time
operating mode or intermittent ventilation.
Setting
no / yes
1 ... 2 ... 6 months
no / yes
Setting
5 ... 30 ... 90 min