6. Electrical work
1
CHECK
ON/OFF
TEMP
E
3
CD
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK
LOUVER
h
A
F
TEST RUN
min
B
SET
RESET
CLOCK
Fig. 6-10
6.3.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
Installed options (high efficiency filter)
Up/down vane setting
Fan speed during the cooling thermostat is OFF
w
When the power supply returns, the air conditioner will start 3 minutes later.
12
2
CHECK
CHECK
4
CHECK
CHECK
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Settings
100 Hr
2500 Hr
No filter sign indicator
Silent
Standard
High ceiling
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup 1)
Equipped with vanes (vanes angle setup 2)
Setting fan speed
Stop
Extra low
2) For wireless remote controller (Fig. 6-10)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1 Going to the function select mode
Press the
CHECK
button F twice continuously.
(Start this operation from the status of remote controller display turned off.)
is lit and "00" blinks.
CHECK
Press the
temp button C once to set "50". Direct the wireless remote controller
toward the receiver of the indoor unit and press the
2 Setting the unit number
Press the
temp buttons C and D to set the unit number "00". Direct the
wireless remote controller toward the receiver of the indoor unit and press the
min
button B.
3 Selecting a mode
Enter 04 to change the power voltage setting using the
D. Direct the wireless remote controller toward the receiver of the indoor unit and
h
press the
button A.
Current setting number:
1 = 1 beep (1 second)
2 = 2 beeps (1 second each)
3 = 3 beeps (1 second each)
4 Selecting the setting number
Use the
temp buttons C and D to change the power voltage setting to 01
(240 V). Direct the wireless remote controller toward the sensor of the indoor unit
h
and press the
button A.
5 To select multiple functions continuously
Repeat steps 3 and 4 to change multiple function settings continuously.
6 Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and press
the
button E.
Note:
Whenever changes are made to the function settings after installation or main-
tenance, be sure to record the changes with a mark in the "Setting" column of
the Function table.
Mode no.
01
w
02
03
04
Mode no.
07
08
10
11
27
h
button A.
temp buttons C and
Setting no. Initial setting
setting
1
2
Ο
1
Ο
2
3
1
Ο
2
3
1
2
Ο
Setting no. Initial setting
setting
1
2
Ο
3
1
2
Ο
3
1
Ο
2
1
2
Ο
3
1
2
3
Ο