Conditions of Acceptability:
Appliance filters inherently have considerable leakage current to the
ƒ
grounding conductor. The leakage current is to be measured in the end
product to determine compliance with the end use requirements.
The filters shall be provided with an overall enclosure suitable for the
ƒ
applicable end product requirements. Mounting means should be
considered in the end use application.
These filters have been judged on the basis of the required spacings in the
ƒ
Standard for Electromagnetic Interference Filters, UL 1283, Fifth Edition.
The suitablity of the grounding means in conjuction with the filter, shall
ƒ
be evaluated in the end use product.
Electrical spacings between uninsulated dead metal parts should be in
ƒ
accordance with the end use application.
The components were submitted and tested with a maximum
ƒ
manufacturer's recommended ambient 45°C as indicated. Suitability of
these devices for use in a higher ambient needs to be determined in the
end use application.
The suitability of filter leads, strain relief and lead terminations shall be
ƒ
considered in the end use application.
The Abnormal Operation Test (Par. 32, UL 1283), (limited short circuit test)
ƒ
was not conducted. Suitability of this device to comply with this
requirement shall be considered in the end use application.