2.2. Wiring
Permitted cross section (diameter) per terminal:
Max..1.5 mm
2
(Ø 0.32 ... 1.4 mm)
Max. number of wires per terminal:
2 x 0.8 mm, 3 x 0.6 mm
• Connect the remaining wires with the auxiliary terminals.
• Only insert connection wires made of the same material and with the
same diameter in a terminal contact.
• Reduce the length of the wires above the mounting box to prevent them
from being clamped when the device is clicked into the mounting box.
• Connect the wires as indicated on the labelling of the mounting box: a
b P P M V1 V2 (top to bottom).
• Respect the following pairs: a/b, P/M,V1/V2
• use a TPVF or YSTY cable 4 x 2 x 0.6 mm or 4 x 2 x 0.8 mm
42
a
b
E
P
P
M
V 1
V 2
EN