SOMFY Connect Weather Station M10 Notice D'installation page 7

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 9
EN
A
MOUNTING
n For exact determination of wind and brightness direction the
Weather Station must be mounted in north alignment (N).
[1] Façade mounted versions
[2] Roof mounted version
1
Mounting with Somfy accessories (
50 mm.
2
Mounting on already existing mast Ø 25 mm.
3
Mounting on already existing mast Ø 50 mm with
Bracket for Weather Station (
[3] n Weather Station must always be installed upright, not
horizontal or in an angle.
CHARACTERISTICS
Weather Station
Supply voltage
Max. current
Operating temperature
Housing dimensions (h, Ø)
Protection class
Degree of protection
Conformity
Accessories
Mast Adaptor
for Weather Station
Ref. 1860321
Dimensions
H: 90 mm/Ø 25 - 50 mm
Sensors
M10
Wind speed
Wind direction
Brightness
Global radiation
Vertical radiation
(0°, 45°, 90°, 135°, 180°, 225°, 270°, 315°)
Twilight
Temperature
Humidity sensor
GPS
Precipitation
CABLE
Connection to ...
Power Supply
RS485 Bus
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for
recycling.
1-3
) on a mast Ø
4
).
24 V DC + 10 %/- 30 %
M25: 230 mA@24 V / M10: 126 mA@24 V
- 30° C...+ 70° C
105 mm, 103 mm
III
IP44 in working position
www.somfy.com/ce
Metallic Mast
1
Ref. 1860335
H: 1 m/Ø 50 mm
M25
Measuring Range
0...35 m/s
1...360°
)
0...100 klux
(x4
(x8)
0...1.200 W/m
2
0...1.200 W/m
2
0...1 klux
- 30...+ 50° C
0...100 % rel. humidity
1/0 (precipitation yes/no) Thermal output, sensor dry, bedewing protection: 0.1 W
Cable
Min.: 2 x 0.3 mm
2
/22 AWG
Max.: 2 x 0.5 mm
/20 AWG
2
Min.: 2 x 0.3 mm
/22 AWG
2
Max.: 2 x 0.5 mm
/20 AWG
2
B
WIRING
n Use rigid cable.
n If a hole has been drilled in the mast during installation
of the unit to fit the cable through, the cable may be dam-
aged by sharp edges.
m The cable for connection of the Weather Station must be
suitable for permanent outdoor use and compliant to the
relevant standards.
C
TOPOLOGY
A.
„xx" represents the bus system handled by the gateway,
e.g. io, SDN, ...
Wall Mount Bracket
2
Ref. 1860336
200 x 90 x 30 (w
d
x
Resolution
Accuracy
0.1 m/s
± 5 % (± 1 m/s) rms over 360°
± 5° with laminar flow and windspeed > 2 m/s
± 200 lux with ± 10 % with ≧ 2 kLux
0.1 klux
1 W/m
± 15 % W/m
2
1 W/m
± 15 W/m
2
± 20 lux with < 100 lux; ± 20 % with ≧ 100 lux
1 Lux
0.1° C
± 1° C with laminar flow and windspeed > 2 m/s
0.1 % rel. humidity
± 10 % rel. humidity at 20° C and wind speed > 2m/s
Thermal output, sensor wet, drying phase: 1.1 W
Twisted pair
Required
Required
Bracket
3
4
for Weather Station
Ref. 1860320
h)
180 x 80 x 80 mm
x
with < 100 W/m
; ± 15 % with ≧ 100 W/m
2
2
with < 100 W/m
; ± 15 % with ≧ 100 W/m
2
2
Max. length
300 m
300 m
animeo Connect . Connect Weather Station . Ref. 5137979A -
2
2
8/20

Publicité

Table des Matières
loading

Ce manuel est également adapté pour: