17
Clip on end cap trims.
Break out marked recess in the cover and clip cover
into position.
18
Determine the required length of centre cover and
saw to size.
Clip on cover and plastic jointing elements.
19
Functional checks
GSR EMR 1, GSR EMR 2:
Open both door leaves and engage hold-open.
Then pull the active leaf closed.
The inactive leaf must be automatically released and
closed.
The active leaf should also close automatically once
the inactive leaf has reached its closed position.
Ensure compliance with instructions for use and also
the safety instructions provided on the test gas
container and safety datasheet.
GSR-EMR 1, GSR-EMR 1G, GSR-EMR 2:
Open active leaf and engage hold-open.
Open inactive leaf and engage hold-open
(not EMR 1G).
Spray test gas (Hekatron 918/5) from a distance of
approx. 10-15 cm towards the smoke chamber.
After approx. 4-6 short bursts, the status display
should switch to alarm (red). If the RMZ is equipped
with the RS alarm module (option), an audible alarm
is also sounded.
The hold-open device is tripped and released, and the
door closes.
The active leaf should also close automatically once
the inactive leaf has reached its closed position.
20
Fit dust protection cover supplied so that dust is
prevented from entering the smoke detector during
any subsequent building or finishing work.
If the dust protection cover is fitted, the unit must be
disconnected from the power supply as the
ventilation slots of the power pack are also covered.
Prior to final commissioning, remove the dust
protection cover and perform a further function
check procedure as described in item 19.
21
Function of the LEDs
LED on
Status display LED 1 (green/red)
Standby: green
Alarm: red
Manual reset necessary: green flashing
(see also item 13)
Service display LED 2 (yellow)
Servicing due: flashes
Contamination: flashes
Fault: continuous
DORMA GmbH + Co.KG
Door Control Division
G - SR EMR
LED off
DORMA Platz 1
D-58256 Ennepetal • Tel. +49 (0) 23 33 / 793-0 • www.dorma.com
Postfach 40 09 D-58247 Ennepetal • Fax +49 (0) 23 33 / 79 34 95
FINAL INSPECTION AND MAINTENANCE
☞
See instruction sheet relating to the use and
application of hold-open systems.
If the RMZ lintel-mounted smoke detector is used in
rooms with a high dust content, ensure compliance
with the specified maintenance intervals. These may
even have to be reduced in order to ensure that dust
deposits in the detector do not give rise to nuisance
tripping.
FURTHER INFORMATION/REGULATIONS
☞
Approval certificate
3) 3) 3) 3) 3)
Instruction sheets relating to the use and application
of hold-open systems
.
3) 3) 3) 3) 3)
Guidelines for hold-open systems
Institute for Building Technology, Berlin, or equivalent
national guidelines.
Some documents are only printed in German as
3) 3) 3) 3) 3)
they refer exclusively to the German market.
3) 3) 3) 3) 3)
published by the