F 1200+
9.4. 1
Emergency-locking of the window
Have the drive disconnected from the 24V supply voltage.
X
Remove the upper side cap (1).
X
Following a power failure the position of the
spindle can be undefined.
Use an Allen key (size 5) to turn the Allen
X
screw (2) of the spindle clockwise up to the
blockage (to end stop).
The spindle now has a defined position.
Turn the spindle anti-clockwise by 3 turns
X
(corresponds to approx. 16 mm stroke).
Now the locking position has been reached.
Make sure that the window is locked correctly.
X
Fit the side cap (1) again.
X
Have the drive connected to the 24V supply voltage again.
X
When the drive is supplied with power again, the window remains in the closed position and is locked.
The drive determines its position and calibrates itself. The window is not moved during this.
1
3×
Faults
2
27