Installation
STEP 1A - Zero U Rack Configuration. Attach the three
mounting clips supplied with the PDU to the rack enclosure
using the included hardware. The mounting clips should be
attached along a vertical plane at equidistant points which
roughly correspond to the center and ends of the PDU. The
exact mounting configuration may vary depending on the rack
and enclosure. If possible, use pre-existing mounting points
within the enclosure.
STEP 1B - Wall or Under-Counter Configuration. Attach the
three mounting clips supplied with the PDU to a wall or similar
flat, secure surface using the included hardware. The mounting
clips should be attached along a vertical or horizontal plane at
equidistant points which roughly correspond to the center and
ends of the PDU. If possible, use pre-existing mounting points.
WARNING: Do not attempt to mount the PDU with the
outlets facing downward; the mounting clips are not
designed to support the weight of the PDU in that
manner.
STEP 1C - Zero U Rack Configuration (Mounting Buttons).
To mount the PDU with the outlets facing inward, align the
mounting buttons on the rear of the PDU with the rack
mounting slots and slide the PDU into position. To mount the
PDU with the outlets facing the rear of the rack enclosure,
remove and discard each of the screws that attach the
mounting buttons to the PDU*. Attach each mounting button
to a mounting bracket using the included M3 screws, and then
attach each mounting bracket to the rear of the PDU (1 at the
top, 1 at the middle, and 1 at the base) using the included
M4 screws (where the mounting button would otherwise be
placed). Position the PDU as desired in the rack enclosure,
align the buttons with the rack mounting slots, and slide the
PDU into position.
* Three M3 screws are included with the mounting hardware
and should be used to attach the mounting button to the
mounting bracket. The screw that was initially used to attach
the mounting button to the PDU should not be used to attach
the mounting button to the mounting bracket or to attach the
mounting bracket to the PDU.
STEP 2: Attach the PDU to the mounting clips. Using an
assistant, place a rear corner of the PDU at an inside edge of
the mounting clips, pivot the PDU toward the alternate inside
edge and snap into place.
STEP 3: Attach each input plug of the PDU to a grounded
outlet. The input plugs, power cords, breakers and outlets are
color-coded to correspond to the two independent power
circuits. WARNING: Attach each input plug to a separate
power circuit. Consult with the electrician at the
installation site if necessary.