TOOLS NEEDED FOR INSTALLATION
• Saber Saw or Jig Saw
• Drill
• 1 1/4" Wood Drill Bit
• Scissors
• Pliers
• Phillips Screwdriver
• Flat Blade Screwdriver
• Wire Stripper or Utility Knife
• Metal Snips
• Measuring Tape or Ruler
• Level
• Pencil
• Caulking Gun
• Duct Tape
PARTS SUPPLIED FOR INSTALLATION
• 1 Hardware Package
• 1 Literature Package
PARTS NEEDED FOR INSTALLATION
• 2 Conduit Connectors
• Power Supply Cable
• 1 Wall or Roof Cap
• All Metal Ductwork
OPTIONAL ACCESSORIES AVAILABLE
• Backsplash
Choose either 24" or 30" high, mounts to the wall
beneath the rangehood for a coordinated look
30" X 24" high part # 6098835 - Stainless
36" X 24" high part # 6098815 - Stainless
30" X 30" high part # 620000095 - Stainless
36" X 30" high part # 620000096- Stainless
• High Ceiling Chimney Kit
One 40" upper chimney to replace 16
chimney that came with hood
part # 620000071 - Stainless
• *Ductless Conversion Kit
For non-vented installations only
* it is highly recommended that professional style
cooking always be vented to the outside
part #620000072 - Stainless
• Replacement Charcoal Filter
For non-vented installations only,
replace charcoal filter as needed
part # 620000041
WARNING
!
PERSONAL INJURY HAZARD
Because of the weight and size of the rangehood
canopy, two or more people are needed to move
and safely install the rangehood canopy.
Failure to properly lift rangehood could result in
damage to the product or personal injury.
This rangehood can be installed as either ducted or ductless. The blower
can be vented through the wall or ceiling. To vent through a wall, a 90° elbow
is used. When installed ductless, the rangehood vents out of grates on the
sides of the chimney. Ductless installations require a Ductless Conversion
Kit, available from your dealer.
WARNING! BEFORE MAKING ANY CUTS OR HOLES FOR INSTALLATION,
DETERMINE WHICH VENTING METHOD WILL BE USED AND CAREFULLY
CALCULATE ALL MEASUREMENTS.
G
upper
1/8"
The ductrun should not exceed 35 equivalent feet if ducted with the required
minimum of 6" round duct. Calculate the length of the ductwork by adding
the equivalent feet in FIGURE 2 for each piece of duct in the system. An
example is given in FIGURE 3.
45˚ Elbow
90˚ Elbow
90˚ Flat Elbow
Wall Cap
For best results, use no more than three 90° elbows. Make sure that
there is a minimum of 24" of straight duct between elbows if more than
one is used. Do not install two elbows together. If you must elbow right
away, do it as far away from the hood's exhaust opening as possible.

PLAN THE INSTALLATION

RANGEHOOD COMPONENTS
F
M
FIGURE 1
CALCULATE THE DUCTRUN LENGTH
3.0 feet
5.0 feet
12.0 feet
0.0 feet
FIGURE 2
A. CANOPY SECTION
B. LOWER CHIMNEY COVER
C. UPPER CHIMNEY COVER
D. MOUNTING SCREWS
E. CHIMNEY MOUNTING
BRACKETS
F. CHIMNEY SCREWS
G. DAMPER
9 Feet Straight Duct
9.0 feet
2 - 90˚ Elbows
10.0 feet
Wall Cap
0.0 feet
Total System
19.0 feet
FIGURE 3