Installation
INDOOR unit terminal block
Morsettiere unità INTERNA
L
dalle morsettiere
from the OUTDOOR unit
dell'unità ESTERNA
terminal block
Magnetic ring
Pass the strap through the
hole in the magnetic ring
to secure it to the cable
S
N
Fig. 38
1 2 3
Fig. 39
REMOTE ON-OFF
For the input of the remote control terminal CN23 (ON-
OFF) and the JR6 quick-release connector
– Remove the JR6 quick-release connector when
using the ON-OFF function;
– When the remote switch is OFF (OPEN), the unit
will be turned off;
– When the remote switch is ON (CLOSE), the unit
will be turned on;
– When the remote switch is opened/closed, the unit
will respond to the request within 2 seconds;
– When the remote switch is ON, the remote/wired
control can be used to select the mode; when the
remote switch is OFF, the unit will not respond to
the remote/wired control request.
When the remote switch is OFF, the remote/wired
control is on, code CP will be shown on the display
board.
– The input voltage is 12 V DC, the maximum design
current is 5 mA.
Fig. 40
31