TWIN UNIT CONNECTION
The 2 indoor units must be connected to the same power supply source.
Connect the E, Y, X terminals of both indoor units with shielded cable.
Indoor unit 1
TWIN configuration
70M + 70M indoor units
140T outdoor unit
105M + 105M indoor units
160T outdoor unit
Indoor unit 2
Outdoor unit power
supply
no.of cables/cross
section
2
4 x 2.5mm
+ G
4 x 2.5mm
2
+ G
Indoor unit power
supply
no.of cables/cross
section
2
2 x 2.5mm
+ G
2 x 2.5mm
2
+ G
Outdoor unit
Fig. 36
Signal
no.of cables/cross
section
2
3 x 0.2mm
3 x 0.2mm
2
29