Common procedures (threaded and flanged devices):
• ONLY install the device in the allowed positions
(figure to the side);
• During installation, avoid debris or metal residues
from getting into the device;
• To guarantee mechanical tension-free assembly, we
recommend using compensating joints, which also
adjust to the pipe's thermal expansion;
• If the device is to be installed in a ramp, it is
the installer's responsibility to provide suitable
supports or correctly sized supports, to properly hold and secure the assembly. Never, for any reason whatsoever, leave the
weight of the ramp only on the connections (threaded or flanged) of the individual devices;
• In any case, following installation, check the tightness of the plant;
• Wiring cannot have cables connected directly to the coil. ALWAYS and ONLY use the connector/electronic board
recommended by the manufacturer;
• Wire the terminal board (31) with a cable 3x1
mm², outside Ø between 8.3 and 9.5 mm using
the relative terminals for cables, as shown in
the general figure on the side. The cable to use
must have double sheathing, be suitable for use
outdoors, with minimum voltage of 500V, and
minimum temperature of 105°C;
To wire the solenoid valve (see the images below):
a. Loosen the 4 fastening screws (1);
b. Remove the cover (2) and loosen the cable gland (3);
c. Pass the cable through the cable gland (3), leaving a suitable length at the end to facilitate wiring to the terminal
board without tensioning or forcing;
d. Secure the cables (duly crimped) to the terminal board (31), connecting terminals 1 and 2 to the power supply and
the earthing cable to the terminal . IMPORTANT: respect the polarity with 24 Vdc power supply;
e. Use a 22mm commercial spanner to secure the cable gland (3), ensuring the product has a protection rating of IP65;
f. Secure the cover (2) with the 4 fastening screws (1). Make sure to place the rubber sealing gasket (33) correctly in
order to ensure product rating of IP65;
• The valve needs to be earthed either through the pipe or through other means (ex. cable jumpers).
a
d
3.3 - INSTALLATION IN PLACES WHERE THERE IS THE RISK OF EXPLOSION (DIRECTIVE 2014/34/EU)
The solenoid valve is not suitable for use in potentially explosive areas.
EV(F)-1-3-6