Warning; Functional Testing - Comelit 47CPZ003 Manuel D'utilisation

Centrale détection de gaz pour chaufferies avec 3 sondes extérieure
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IST-47CPZ003
Valve: The manually resetting
indicated position and should be protected
The Fig.2
Mounting:
shows the instrument size. It has to be wall-mounted by four screw anchors.
and closes with the 4 screws on the cover.
IMPORTANT: T
O AVOID IRREVERSIBLE DAMAGE
-
OR BEFORE UNPLUG OR RE
CONNECT THE FLAT CABLE
Only if necessary, for maintenance or installation requirements, the housing cover can be separated from its base,
first remove power supply, then disconnect the flat cable, press on the two side tabs as shown
it, push the flat cable into the connector, respecting the polarization, the two levers close automatically locking it.
Only then you can reconnect power supply.
Cable glands: the lower side of the housing has 3 inputs designed for metric cable glands (M20x1.5 that accept
external cables Ø 6÷12 mm). These passages are closed, but they are not
installation requirements, they must be drilling. To facilitate the operation, they have a centering for the drill bit.
Electrical Connection:
the gas detection system. The device, clearly identified, must act only on Phase and Neutral. If it is necessary, you
may install a surge or lightning protector, etc.
The instrument is supply with non-reversible and plug-in terminals. Therefore the cables should be anchored to the
case in order to avoid terminal overstress. The connection to the control unit does not need any hearting. The remote
sensor can be placed at a max. distance of 100 meters from the control unit with a cable of 3x1.5mm
of 200 meters using a 3x2.5 mm
Fig. 4
shows the 110÷230VAC powering connection with normally open manual resetting valve and alarm siren
24V.
Fig. 5
shows the 110÷230VAC powering connection with normally closed manual resetting valve and alarm siren
24V.
Fig. 6
shows the 24VDC powering connection with both 24VDC alarm siren and normally closed manual resetting
valve with, for example, power supply unit (max load 2,5A) with No.2 internal 12V/7Ah Pb battery to maintain the
system powered on in absence of Main power supply.
Dip-Switch Setting:
Before powering unit, you must configure the Dip-Switches on the circuit in the
Enable/Disable:
SW1 Dip Switches No.1, No.2, No.3 enable or disable the corresponding input of the remote
gas detector
control unit functioning).
ON = Enabled input The detector is installed, the Led Bar and the Fault Relays and Miscel-
laneous are in operation. (
OFF = Input DISABLE The detector is absent, the Led Bar is off. Fault relays and alarms do
not intervene. (can also be used to exclude a faulty detector or removed for maintenance).
SET AUX:
SW2 Dip-Switch No.1 selects AUX input
OFF = contact lenses for eg contact. Manual button (DEFAULT SETTING)
ON = control of NC Valve Solenoid Valve with Location Sensor.
In Fig. 7 Schematic and Configuration of SW2 Dip-Switch No.1 to use the AUX input to check if the Valve has
actually been closed. Valves need to be reassembled with NC Position Sensor.
In Figure 8 Connection Schedule and Configuration of SW2 Dip-Switch No.1 to use the AUX input, placed on the
board in the cover with a NA contact. For example, a manual alarm button.
Thresholds: the SW2 Dip-Switches / No.2 and No.3 set the alarm thresholds. See Table 2.
Relay
No.2 and No.3 both OFF = ALARM 1 set to 10%LEL and ALARM 2 set to 20%LEL (DEFAULT SETTING)
No.2 ON and No.3 OFF = ALARM 1 set to 15%LEL and ALARM 2 set to 20%LEL
SW2 Dip-Switch No.4 sets the function of the ALARM 2 relay.
Logic of
Relay:
ON = Negative logic, the relay is de-energized, it is used for normally open valves.
OFF = Positive logic, the relay is normally energized, in case of power failure or relay failure, it auto-
matically moves to the alarm position. It is used for normally closed valves.

WARNING

Configure Dip-Switches before powering the control panel.
The detector doesn't need adjustments after being installed.
During preheating of the detectors, which is of about 60 seconds, the alarm relays remain inhibited, while the
FAULT
Yellow LED and the
In case of short circuit between the connection cables to a detector, the protection circuit interrupts to it the
Both the FAULT relay and the yellow LED will activate.
power supply.
the short circuit, and then turn on the unit.
If a detector is not
installed, to avoid automatic

FUNCTIONAL TESTING

Periodical testing: we advise to carry out working tests every 6-12 months.
specific users's manual.
PAY ATTENTION: This procedure has to be made with extreme attention and by authorized and trained people.;
because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices.
The TEST key is deactivating when an alarm condition occurs.
Comelit Group S.p.A. - Via Don Arrigoni 5 - 24020 Rovetta S. Lorenzo BG Italy
Istruzione / User's Manual / Manuel d'utilisation
solenoid
valve for the gas cut-off should be installed outside the room in a clearly
from direct sunlight and
,
DISCONNECT THE POWER SUPPLY TO THE CONTROL PANEL
.
The installation must be provided for the mains, a bipolar disconnect switch dedicated for
2
cable. It is not necessary to use shielded cables.
(SENSOR-1, SENSOR-2 and
FOR DEAULTS ARE ALL CONFIGURED
relay are activated.
rain.
SENSOR-3). (No. 4 is not used and its position does not affect the
operation.
Turn off the 47CPZ003, remove the cause of
FAULT
relay operation you must
The housing opens
,
DURING INSTALLATIO
in Fig.
3.
manually
breakable, according to the
2
or to a distance
housing
ON)
disable
the corresponding input.
For remote detectors, refer to the
Tel. +39 0346 750 011 - Fax +39 0346 71436
Pag.5/9
(
)
WIRING CABLES
To reconnect
cover.