360-45010
390-40011
- Off delay: only adjustable below CH1, but functions identically for all active channels (max. 3
channels).
After the last detected movement, the system counts down the 'off delay'. If the set time elapses
before a new movement is detected, the load (lighting) is switched off for all active channels.
Adjustable between: 1 – 60min; standard 10min
- Loadshedding X: energy-saving switch (fig.1)
In case of a closed contact, this value is taken as setpoint. The value lies below the actual setpoint
(lux), as a result of which the lighting is only switched on in case of a lower level of daylight.
Application: close the energy-saving switch in order to save energy at specific moments.
Adjust Settings:
- Copy settings:
1) Custom to Backup: the settings in custom mode are copied to backup mode
2) Backup to Custom: the settings in backup mode are copied to custom mode, so making
changes is possible.
3) Factory to Custom: the factory settings are loaded in custom mode.
4) Factory to Backup: the factory settings are loaded in backup mode.
You are recommended to always make a backup of the settings. After you have done this, preferably
work in backup mode (see '4.1. GENERAL SET' and 'Quickguide', A and D).
- Initiate sensor:
If the system is started without the light sensor is connected or if you have the impression that the
light sensor measures wrong values, you can best initiate the sensor once again.
4.3. Status (see 'Quickguide', D)
In this menu, you can view the status of a number of parameters (see 'Quickguide', D).
Ch1..............channel 1
Ch2..............channel 2
Ch3..............channel 3
42
EN