Troubleshooting - Lutron Energi Savr Node EcoSystem Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Energi Savr Node
Using LEDs to troubleshoot
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker or isola-
tor before wiring or servicing the Energi Savr Node with
EcoSystem unit.
Buttons and LEDs in the unit are used for troubleshooting.
If wiring is exposed when accessing buttons and LEDs, the
unit must be accessed by a certified electrician, following
local codes.
LED Behavior
Normal
Problem
LED
operation
indicator
Green:
Green: 5 flashes
PWR (Power)
Continuous On
per second
Red:
Continuous on
Red/Green:
alternating 1 flash
ECO1
Green: 1 flash
per second
ECO2
per second
(EcoSystem
Red: 1 flash per
second
Status)
Red: 5 flashes per
second
Red: 1 flash per 7
seconds
Green: 1 flash per
7 seconds
Green: 1 flash
Green: 5 flashes
QS (QS Link)
per second
per second
Off
Green:
Off
Flashing
Ethernet
Yellow:
Off
Continuous On
Red: 5 flashes per
second
Test
Off
Green: 5 flashes
per second
Red: 5 flashes per
second
Temp
Off
Red: continuous
On
Energi Savr Node
with EcoSystem
TM
English
with EcoSystem
TM
Probable cause
General system failure
EcoSystem link
externally shorted,
miswired or link error
Link slowed because of
over-temperature
Link stopped because of
over-temperature
Emergency Mode
More than one supply
powering link
Link disconnected,
communication lost
Incorrect data
No connection ever
made
Ethernet not connected
Ethernet not connected
Test failed
Test mode activated
Over-temperature
Over-temperature, unit
disabled
Installation Guide
®
Español
Français
|
Installation Guide
®
Input LED Behavior
LED
LED Behavior
Continuous On
Occ
(Occupancy
1 flash per second
Sensor)
Off
Continuous On
Daylight
Flashing
(Daylight
Sensor )
Off
Continuous On
IR
(Infrared
Flashing
Receiver)
Off
Continuous On
CCI
(Contact
Flashing
Closure Input)
Off
Emerg
Continuous On
(Emergency
Contact Closure
Rapid flash
Input)
Português
Description
Sensor detects Vacancy
Sensor detects Occupancy
Sensor never detected
Sensor is detected
Sensor information
transmitting on the QS link
Sensor never detected/sensor
not seeing light
Receiver is detected
IR button press detected
Receiver never detected
Contact detected/open
Contact closed
Contact never detected
Normal operation/Contact
Closed/Jumpered
Emergency Mode/Contact
Open/Jumper missing
Lutron