Mohlenhoff RD 40203 Mode D'emploi page 45

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 52
Start the entry by activating the function "PAr".
Select the individual ciphers of the parameter number by rotat-
ing and confirm by pressing.
Activate the entry by selecting "SET" and by pressing.
Perform the setting according to the subsequent parameter list.
Return to the basic level by selecting "BACK" 2 times.
If no operation is performed, the display returns to the basic
level after approximately 30 seconds.
No. Description
Heating system
Sets the existing heating system:
• Floor heating, standard (FBH St.)
010
• Floor heating, low energy (FBH NE)
• Radiator (RAD)
• Convector, passive (KON pas)
• Convector, active (KON akt)
Blocking of cooling
020
Deactivates the cooling function.
Operating lock
030
Protects the deactivation of the operating
lock with a PIN.
PIN operating lock
Sets the PIN for parameter 30.
If PIN is unknown:
Disconnect the device from the
mains network.
031
Hold down the rotary control and
apply voltage again until the soft-
ware version is shown on the dis-
play and goes out again.
Press the rotary control again until
the symbol
disappears.
Operation
Setting
0 = FBH St.
1 = FBH NE
2 = RAD
3 = KON pas
4 = KON akt
Standard: 0
0 = activated
1 = deactivated
Standard: 0
0 = deactivated
1 = activated
Standard: 0
0 ... 9999
Standard: 0000
DEU
ENG
ENG
FRA
NDL
ITA
ESP
45