List Of Coded Errors - Chauvin Arnoux C.A 6030 Notice De Fonctionnement

Masquer les pouces Voir aussi pour C.A 6030:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

7. LIST OF CODED ERRORS

Error
code
Er02
Incorrect wiring or connection error: L and PE reversed
Er03
Incorrect wiring or connection error: L missing
Er07
Earth potential too high (potential danger): measurement STOPPED
Untimely interruption of the current during the measurement of Z
Er08
tripped?)
Er10
Voltage too high on the voltage probe (potential danger): measurement STOPPED
Er11
The RCD tripped during the non-tripping test (leakage current too high?)
Er12
RCD defective in pulse mode.
Phase voltages not of the same order of magnitude (phase-to ground and phase-to-phase
Er15
voltages mixed)or the signals L1 and L3 are equal.
Er16
Frequency not sufficiently stable.
Er17
The maximum time allowed to acquire the voltage on U
Er18
Current probe not connected.
Er19
The type of test chosen is not compatible with the assigned current of the RCD
Er23
RCD defective in sweep mode.
Meaning
is exceeded.
32
76
(earth fault breaker
LPE

Publicité

Table des Matières
loading

Table des Matières