Chloride Active

8.1.2 Battery Packs

UK
Housing
Battery arrangement
Protection
Size (WxHxD, mm)
Weight (kg)
Operating temperature
Storage temperature
Altitude
Relative humidity

8.2 Runtime charts

Theoretical values with fully charged batteries and resistive load.
NOTE: The maximum quantity of external battery packs that can be connected to the UPS is four.
Active 700 T:
Active 1000 T and Active 1000 RT:
40
945044.066
BP-A1000/1500-T
Tower
2x3x7,2Ah
Breaker 70A/80Vdc
MECHANICAL
157x245x438
20
ENVIRONMENTAL
Load
55W
110W
170W
225W
280W
335W
390W
450W
505W
560W
UPS
Load
UPS
+ 1 BP
80W
63 min
239 min
160W
37 min
158 min
240W
26 min
91 min
320W
20 min
69 min
400W
15 min
55 min
480W
13 min
45 min
560W
11 min
38 min
9 min
33 min
640W
720W
7 min
29 min
800W
6 min
25 min
BP-A1000/1500-RT
Rack/Tower
2x3x7,2Ah
Breaker 70A/80Vdc
438x86(2U)x438
32
0 - 40 ºC
-15 ºC / +40 ºC
0-3000m
10% to 90%
UPS
51 min.
35 min.
24 min.
18 min.
15 min.
12 min.
10 min.
8 min.
7 min.
5 min.
UPS
UPS
UPS
+ 2 BP
+ 3 BP
+ 4 BP
438 min
661 min
861 min
254 min
397 min
476 min
197 min
262 min
372 min
145 min
212 min
263 min
97 min
174 min
220 min
80 min
136 min
191 min
69 min
99 min
161 min
60 min
86 min
130 min
51 min
75 min
99 min
46 min
67 min
89 min
BP-A2000/3000-RT
Rack/Tower
2x6x9Ah
Breaker 70A/80Vdc
438x86(2U)x657
52