8 Specifi cation and back-up times
UK
8.1 Specifi cation
NOTE: We reserve the right to modify the information in these tables without prior notice.
8.1.1 Uninterruptible Power Supplies
UPS Rating
Housing
Technology
Output Power
(VA/W)
Nominal input
voltage (VAC)
Operative input
voltage range (VAC)
Nominal input
frequency (Hz)
Operative input
frequency range
(Hz)
Input power factor
Waveform
Nominal output
voltage (VAC)
Voltage regulation
(%)
Output frequency
(Hz)
Harmonic distortion
(linear/non-linear
load) THDv
Transfer time (line-
battery-line) (s)
Overload capacity
(line mode, output
power factor 0.9)
Shortcircuit
protection
Type
Arrangement
Advanced Battery
Care
Battery
management
Size (WxHxD, mm)
Weight (kg)
38
945044.066
Active
Active
Active
700 T
1000 T
1000 RT
700VA
1000VA
Tower
Tower
Rack/Tower
700/630
1000/900(*)
120V-284V (depending on output load)
50/60Hz +/-5% (40/70Hz if Frequency Converter Mode is activated)
200(**) / 208(**) / 220 / 230(default) / 240 V (confi gurable via user software and optional LCD
50/60Hz ±0,5% (same as input or selectable in Frequency Converter Mode)
<110% warning // 111-130%: 12 seconds (UPS to bypass) // >130%: 1,5 seconds (UPS off)
Sealed maintenance-free lead acid (VRLA)
1x2x7,2Ah
1x3x7,2Ah
Battery pack auto detection, automatic runtime calculation, protection against deep discharge
MECHANICAL
157x245x438
157x245x438
13
15
Active
Active
1500 T
1500 RT
1500VA
Tower
Rack/Tower
Advanced on-line double conversion
1500/1350(*)
INPUT
200-240V
50/60Hz auto-selection
0,99 (batteries charged)
OUTPUT
Pure sinusoidal
Display) (250 V under request)
3%
Max. 4% / Max. 8%
0
Yes
BATTERIES
1x3x9Ah
Yes
438x86
157x245x488
(2U)x482
18
18
Active
Active
2000 RT
3000 RT
2000VA
3000VA
Rack/Tower
Rack/Tower
2000/1800(*)
3000/2700(*)
140-284V (depending on
output load)
1x6x7,2Ah
1x6x9Ah
438x86
438x86
438x86
(2U)x482
(2U)x657
(2U)x657
20
26
31