Macurco GD-6 Instructions D'utilisation page 18

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

c.
The alarm relay will be closed, so any devices connected to that relay will be tested.
d.
The Fan relay will be activated for the next 1 minute of the test, so if the fan circuits are wired in the normal
manner, the fan should run.
e.
The 4-20mA output will then ramp up from 4 to 16 mA over the next 130 seconds of the test, so if the circuit is
wired in the normal manner, the control panel or building automation system should respond.
f.
At the end of the test cycle, the light will turn green and be on steady (Normal Operation), the fan & alarm relay will
be in standby mode and the 4-20 mA output will return to 4 mA (in clean air).
8. When testing is completed reassemble the unit or units.
Manual Operation Test
This option gives the user the opportunity to manually initiate an individual test for each relay, the analog output and the sensor
response to gas. From normal operation mode press the Next button 3 times to get to the Test Mode (tSt). Press the Enter button once
to get into the Test Menu. Press the Next button to scroll through the four test options and press Enter to initiate the selected test. Note
that if the relay or 4–20 mA output has been disabled, the test selection will not be displayed in the test menu.
bUZ –Buzzer test, 3 seconds
Art - Alarm Relay Test, 10 seconds
Frt - Fan Relay Test, 60 seconds
42t - 420 loop test, 25 seconds
gtS - Gas Test, 3 minutes (no output to the panel during the gas test)
The display will flash during the test or in the case of the gas test the level will alternate with the expected gas (mE, Pro or Hy). Once
the test is complete, the display will return to steady display. To exit the test menu, press the Next button until "End" is displayed, then
press Enter to return to normal mode.
Combustible Gas Gas Test
The following steps must be performed when conducting a calibration or calibration verification test (bump test) to ensure proper
performance of the monitor. Failure to do so may adversely affect product performance and result in sickness or death.
When performing a calibration or calibration verification test (bump test) only use certified calibration gas at the
required concentration level. Do not calibrate with expired calibration gas.
If the instrument cannot be calibrated, do not use until the reason can be determined and corrected.
Do not cover or obstruct display or visual alarm cover.
Ensure sensor inlets are unobstructed and is free of debris
General
The GD-6 can be bump-tested or calibrated with the GD-6 Field Calibration Kit using Methane, Propane or Hydrogen gas, regulator and
test hood, available through your local representative or from Macurco.
! WARNING
18

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gd-12

Table des Matières