Display Channels; Adjustment Channels - Resol EM Manuel

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5.2

Display channels

Error code display
EC
Error code
Display range: 0, 2
0 = OK
2 = Bus error (there has been no bus communication for approx. 1 minute)
Version compatibility display
VC
Version compatibility
Display range: 0, 4
This channel indicates if the controller connected has been recognised by the mod-
ule.
If 0 is indicated, the controller has not been recognised or the bus communication
is faulty.
If 4 is indicated, the extension module has recognised the controller and is function-
ing normally.
Display of sensor temperatures
S1 ... S6
Display of measured values
Display range: -40 ... +260 °C
Only if a sensor is connected to the corresponding terminal, will a value be displayed.
In the case of a line break or if no sensor is connected, 9999 will be displayed.
In the case of a short circuit, 0 will be displayed.
Display of speed
R1 ... R5
Display of speed / status
Display range: 0 ... 100 %
These channels indicate the current speed values of the relays. R5 is a potential-free
relay not suitable for speed control. Therefore, its status is indicated with 0 % or
100 % respectively.
Display of the software version
PG
This channel indicates the version number of the firmware.
Display of the version number
VN
This channel indicates the version number of the hardware.
5.3

Adjustment channels

Manual mode
M1 ... M5
Adjustment range: OFF, Auto, On
Factory setting: Auto
In the channels M1 to M5, the corresponding relays can be switched on or off, or
set to automatic mode manually.
Manual mode
MM
Adjustment range: 0 ... 5
Factory setting: 0
The adjustment in this channel determines which relays are switched on when the
slide switch below the display is set to I.
0 = Relay 1 on, all others off
1 = Relays 1 and 2 on, all others off
2 = Relays 1 and 5 on, all others off
3 = Relays 1, 2 and 5 on, all others off
4 = Relays 1 and 4 on, all others off
5 = Relays 1, 4 and 5 on, all others off
Selecting the sensor type
T1 ... T6
Adjustment range: 0 ... 4
Factory setting: 0
In this menu, a sensor type can be selected for each sensor input. The following
adjustments are available:
0 = Resistance (the measured resistance will be displayed independent of the sensor
type connected)
1 = Pt1000
2 = KTY
3 = PT500
4 = RTA (remote control)
Note
The adjustments made in the channels T1 ... T6 only determine the display
of the measured values in the channels S1 ... S6 of the extension module.
Î Adjust the sensor type in the controller connected as well!
29