2.2

Electrical connection

Electric shock!
WARNING!
Upon opening the housing, live parts are exposed!
Î Always disconnect the controller from power supply
before opening the housing!
ATTENTION!
ESD damage!
Electrostatic discharge can lead to damage to electronic com-
ponents!
Î Take care to discharge properly before touching the
inside of the device!
Note
Connecting the device to the power supply must always be the last step
of the installation!
Do not use the device if it is visibly damaged!
The device is equipped with 4 semiconductor relays and 1 potential-free relay to
which loads such as pumps, valves, etc. can be connected.
Depending on the product version, the mains cable and the sensor cables are already
connected to the device. If that is not the case, please proceed as follows:
Connect the temperature sensors (S1 to S6) to the corresponding terminals
with either polarity:
1/2
sensor 1 (e.g. flow HC2)
3/4
sensor 2
5/6
sensor 3
7/8
sensor 4
9/10
sensor 5
11/12
sensor 6
Potential-free relay:
15
conductor R5-A (normally open contact)
16
conductor R5-M (normally closed contact)
17 ... 21
ground terminal ⌯
Semiconductor relays:
22
neutral conductor R4
23
normally open contact R4
22
24
neutral conductor R3 (e.g. mixer closed HC2)
25
normally open contact R3 (e.g. mixer closed HC2)
26
neutral conductor R2 (e.g. mixer open HC2)
27
normally open contact R2 (e.g. mixer open HC2)
28
neutral conductor R1 (e.g. pump HC2)
29
normally open contact R1 (e.g. pump HC2)
17 ... 21
ground terminal ⌯
Connect the mains cable to the following terminals:
30
neutral conductor N
31
conductor L
17 ... 21
ground terminal ⌯
Attach flexible cables to the housing with the enclosed strain relief and the cor-
responding screws.
The device is supplied with power via the mains cable. The mains voltage must be
100 ... 240 V~ (50 ... 60 Hz).
2.3

Data communication / Bus

The device is equipped with a RESOL VBus
controller. Carry out the connection at the two terminals marked VBus (any
polarity).
13/14
VBus terminals
The VBus
cable can be extended or replaced with a two-wire cable (bell wire; the
®
cross section must be at least 0.5 mm²). The cable can be extended to up to 50 m in the
case that one module is used. The distance can be increased by using a VBus
IP 20
EM
Made in Germany
S1
S2
S3
S4
S5
S6
1
2 3
4
5
6
7
8
9 10 11 12 13 14
sensor terminals
potential-free relay
®
for data communication with the
R1-R4 1 (1) A (100 ... 240) V~
VBus
15
16
17 18 19 20 21
VBus
®
ground common
terminal block
®
-Repeater.
T4A
100 ... 240 V~
R5
4 (1) A (100 ... 240) V~
50-60 Hz
N
R4
N
R3
N
R2
N
R1
N L
22
23 24 25 26 27 28 29 30 31
load terminals
mains terminals