SYMPTOM
PROBABLE CAUSE
No data shows in the
Charge controller not communicating
View Charge Unit
with IPN-ProRemote
Status screen
Days since last
The day counter increments once each 24
equalize or full charge
hours since battery power was applied.
shows 1 day too many
Days since last
Day counter updates when equalize
equalize reset without
starts
equalize completing
Net battery current
Signal wires on shunt reversed
polarity reversed
Battery current seems
Some charging sources or loads do not
inaccurate
go through shunt
Shunt wiring incorrect or faulty.
Shunt signal wires picking up electrical
noise
Excessive voltage drop in network cable
to IPN-ProRemote or in system power
wiring
Net battery current not reading 0.0A with
zero amps flowing
Remaining Battery
Charge controller has not finished
Capacity & Amp-
charging battery
Hours From Full show
dashes (– – –)
Remaining Battery
Shunt not properly reading net battery
Capacity or Amp-
current
Hours From Full seem
inaccurate
Incorrect battery amp-hours entered
Incorrect Charge Efficiency factor
Battery not fully charged for an extended
period
Charge controller is not what normally
fully charges the battery
Self Discharge Rate set incorrectly
Temperature sensor faulty
ITEMS TO EXAMINE OR CORRECT
Controller-to-controller network cable not wired A-to-A, B-to-B, or wires are open or
short.
More than one charge controller is set to be Master or more one charge controller
set to same slave address.
Normal operation. This potential 1 day error may be eliminated by rebooting the charge
controller in the middle of the night so that the counter increments at this time rather
than during the day.
Normal operation. The equalize day counter is reset when equalize starts rather than
when it ends.
Swap signal wire positions on shunt.
Confirm that no other current carrying conductors other than the shunt cable is
connected to battery negative.
Shunt wired in series with battery positive, should be negative.
One or both shunt signal wires open or short.
Confirm signal wires are twisted pairs.
Consider using shielded twisted pair cable for signal wires.
Relocate signal wires away from power or noise generating wiring.
Confirm that with backlight ON and with highest possible charge or discharge current
flowing in system, voltage difference between "COM test point" and "SHUNT –" on
the back of the IPN-ProRemote is less than ±1.0V at all times, with less voltage
drop being better. Correct wiring as necessary. Consider not using backlight.
Perform Reset Current Shunt Zero function exactly as described in this manual to
remove zero offset.
Normal operation. Remaining Battery Capacity & Amp-Hours From Full displays
show dashes until the battery is fully charged which initializes amp-hour counting.
Net battery current must read correctly to properly count Amp-Hours From Full,
which is used to compute Remaining Battery Capacity. See Battery Current Seems
Inaccurate.
Confirm correct 25°C 20Hr rate battery amp-hour value.
Confirm Charge Efficiency factor and Charge Efficiency Mode are set correctly.
Incorrect net battery current readings can cause Charge Efficiency to become very
inaccurate. Reset to 94%.
Since battery charge / discharge behavior is not ideal, error in the Amp-Hours From
Full counter builds as the battery cycles without becoming full. Try to fully charge
the battery often.
To get the best accuracy, the charge controller should be what normally or at least
regularly brings the battery back to full charge.
Confirm proper 25°C value is entered.
Many factors are temperature compensated. Confirm proper temperature sensor
operation as described in the charge controller manual.
Installation and Operation Manual