INSTALLATION AND ELECTRICAL CONNECTIONS
INSTALLATION
Before connecting the regulator EPP4, pay attention to the
following instructions:
Connect the regulator as close as possible to the apparatus
which will be regulated (resulting in higher precision and
shorter response times);
Piping section of pressure supply should be sufficiently large;
Connect the air filter (50µ, Dew point 2°C) upstream from the
regulator, and a lubrificator if necessary, downstream;
It is recommended to mount the regulator in a vertical position,
electronic on top.
Set up the inlet pressure (max.: see page 2).
Connect the regulator to the pneumatic network.
Connect the pressure supply on the inlet port P and the regulation
circuit with the outlet port A.
Fluid: lubricated (1 gr/m
It is recommended to use a silencer in the exhaust R.

ELECTRICAL CONNECTIONS

Power supply
DC – Supply 24 V ± 15 %
In case of rectified voltage supply
(from AC to DC) the residual ripple
should be smaller than 1V
V
27.6
24
20.4
Electrical connection diagrams
Disconnect the installation prior to any intervention
on the electrical supply cable. Do not invert polarity.
maku GmbH & Co. KG · 73630 Remshalden · Telefon (0 71 51) 90 39 50 · Telefax (0 71 51) 90 39 5 99 · www.maku-industrie.de
maxi) or non lubricated air and neutral gas
3
Parker Lucifer SA
Ch. du Faubourg de Cruseilles 16
CH-1227 Carouge-Geneva, Switzerland
Tel. : +41 22 3077 111
Fax.: +41 22 3077 110
496783
The main connector (A) adopted is a standard 8 pole-M12
The female connector to mount is the 8 pole M12 connector (IEC
61076-2-101 model LF).
Example:
Binder
79-3580-32-08
Compona
188 690-1
The information/programming connector (B) is a standard 5 pole M12
connector:
The female connector to mount is the 5 pole M12 connector (IEC
61076-2-101 model LF).
Example:
Binder
79-3430-33-04
Compona
188 530-5
Use only straight connectors to keep access free for
both connectors
- 5 -
EPP4 Pressure Regulator
http://www.binder-connector.de/
http://www.compona.ch/
http://www.binder-connector.de/
http://www.compona.ch/
408193.doc – Rev.0 / 12.11.2009
:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

P4cg42 serieP4cg6 serieP4cg9 serieP4cg4101

Table des Matières