ICAR PQS
P15.04
Remote access password
P15.01 – If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P15.02 – With P15.01 enabled, this is the value to specify for activating user level access. See Password access chapter.
P15.03 – As for P15.02, with reference to Advanced level access.
P15.04 – If set to a numeric value, this becomes the code to specify via serial communication before sending commands from a remote control.
(*) Available value only if the controller is not installed on the ICAR cabinet
M16 –COMMUNICATION (COMn,n=1...2)
P16.n.01
Node serial address
P16.n.02
Serial speed
P16.n.03
Data format
P16.n.04
Stop bits
P16.n.05
Protocol
P16.n.06
IP address
P16.n.07
Subnet mask
P16.n.08
IP port
P16.n.09
Channel function
P16.n.10
Client/server
P16.n.11
Remote IP address
P16.n.12
Remote IP port
P16.n.13
IP gateway address
Note: this menu is divided into 2 sections for communication channels COM1..2.
The front IR communication port has fixed communication parameters, so no setup menu is required.
P16.n.01 – Serial (node) address of the communication protocol.
P16.n.02 – Communication port transmission speed.
P16.n.03 – Data format. 7 bit settings can only be used for ASCII protocol.
P16.n.04 – Stop bit number.
P16.n.05 – Select communication protocol.
P16.n.06, P16.n.07, P16.n.08 – TCP-IP coordinates for applications with Ethernet interface. Not used with other types of communication modules.
P16.n.09- Role of the communication channel. Slave=Slave Modbus. Gateway=Bridge between Ethernet and serial ports. Mirror=Remote panel mirror
(reserved/function not operative yet)
P16.n.10- Enabling TCP-IP connection. Server=Awaits connection from a remote client. Client=Establishes a connection to the remote server.
P16.n.11...P16.n.13- Coordinates for the connection to remote server when P16.n.10 is set to Client.
M17 – BASIC PROTECTIONS
P17.01
Temperature unit of measure
Panel interior temperature measurement
P17.02
source
P17.03
Channel nr. (x)
P17.04
Fan start temperature
P17.05
Fan stop temperature
P17.06
Panel interior temperature alarm threshold
P17.07
Capacitor current overload
P17.08
Capacitor current overload threshold
P17.09
Immediate step disconnection threshold
P17.10
Current overload alarm reset time
P17.11
Step trimming
P17.13
Maximum voltage threshold
P17.14
Minimum voltage threshold
OFF
Psw (M15)
UoM
Default
Usr
01
Usr
bps
9600
Usr
8 bit – n
Usr
1
Usr
(various)
Usr
192.168.1.1
Usr
255.255.255.0
Usr
1001
Usr
Slave
Usr
Server
Usr
000.000.000.000
Usr
1001
Usr
000.000.000.000
Psw (M15)
UoM
Adv
Adv
Adv
Adv
°C/°F
Adv
°C/°F
Adv
°C/°F
Adv
Adv
%
Adv
%
Adv
min
Adv
Adv
%
Adv
%
42 / 86
OFF/1-9999
Range
01-255
1200
2400
4800
9600
19200
38400
57600
115200
8 bit, no parity
8 bit, odd
8bit, even
7 bit, odd
7 bit, even
1-2
Modbus RTU
Modbus ASCII
Modbus TCP
000.000.000.000 –
255.255.255.255
000.000.000.000 –
255.255.255.255
0-9999
Slave
Gateway
Mirror
Client
Server
000.000.000.000-
255.255.255.255
0-9999
000.000.000.000-
255.255.255.255
Default
Range
°C
°C
°F
Internal sensor
Internal sensor
AINx
NTCx
1
1-99
25
0-212
20
0-212
55
0-212
OFF
ON
ON
50
OFF / 0 – 150
83
OFF / 0 – 200
15
1 – 30
ON
OFF / ON
110
OFF / 90...150
90
OFF / 60..110
rev9 jan19