ICAR PQS
The controller displays the imminent connection or disconnection of the steps with the flashing of their identification number
(above). The flashing can last in cases in which the insertion of a step is not possible due to the reconnection time (discharge time
of the capacitor). If the number above step is light gray, it means that the step is not available because its reconnection time is not
yet expired. The device then waits for the end of the reconnection time.
4.3
TEST Mode
The activation and deactivation of the outputs is done as for the manual mode, but without considering the reconnection time.
Once in programming and parameters are set, the unit will automatically exit the test mode.
If you need to enter TEST mode use the appropriate command in the Command menu.
5
MAIN MENU
The main menu is made up of a group of graphic icons (shortcuts) that allow rapid access to measurements and settings.
Starting from normal viewing, press key. The main menu screen is displayed. Press ▲▼ to rotate clockwise/counter clockwise
to select the required function. The selected icon is highlighted and the central part of the display shows the description of the
function. Press to activate the selected function.
If some functions are not available, the correspondent icon will be disabled, that is shown in a light grey colour.
etc. - Shortcuts that allow jumping to the first page of that group. Starting from that page it is still possible to move
forward-backward in the usual way.
- Switch the operation to manual or automatic mode.
–Opens the password entry page, where it is possible to specify the numeric codes that unlock protected functions (parameter
setting, commands menu).
– Access point to the setup menu for parameter programming. See dedicated chapter.
– Access point to the commands menu, where the authorised user can execute some clearing-restoring actions.
6
PASSWORD ACCESS
The password is used to enable or lock the access to setting menu (setup) and to commands menu. For brand-new devices (factory
default), the password management is disabled and the access is free. If instead the passwords have been enabled and defined,
then to get access, it is necessary to enter the password first, specifying the numeric code through the keypad. To enable password
management and to define numeric codes, see setup menu M15 Password. There are two access levels, depending on the code
entered:
User-Level access (Usr) – Allows clearing of some recorded values and the editing of a restricted number of setup
parameters.
Advanced access level (Adv) – Same rights of the user access plus full settings editing-restoring.
From normal viewing, press to recall main menu, select the password icon and press .(fig..1) The display shows the screen
in picture (fig.2):
Keys ▲and ▼change the selected digit (fig.3)
Keys ◄ and ► move through the digits (fig.4)
Enter all the digits of the numeric code, then move on the key icon. If the password code entered matches the User access code
(password:1000) or the Advanced access code (password:2000 Available value only if the controller is not installed on the ICAR
cabinet) , then the correspondent unlock message is shown. Once unlocked the password, the access rights last until:
the device is powered off.
the device is reset (after quitting the setup menu).
the timeout period of two minutes elapses without any keystroke.
To quit the password entry screen press key.
fig.1
Password
entry
Comands
Setup menu
System info page
harmonics
fig.2
Switches to
Main page
manual mode
Switches to
automatic mode
Voltage – current
Power page
Step life
statistics
fig.3