Target Power Factor Set-Up; Harmonic Analysis Page - Icar RPC 8BGA Manuel Complet

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ICAR PQS
Energy meters
Push ▼
Event log
Push ▼
Expansion status
Push ▼
Real time clock
Push ▼
System info
Push ▼
Service
Note: Some of the pages listed above may not be displayed if the relevant function is disabled. For example, if the limit function is
not programmed, the corresponding page won't be shown.
8

TARGET POWER FACTOR SET-UP

To set the desired power factor from the main page
press twice the button ▲ appears the page of the setting of desired power factor:
using the ◄ and ► buttons to increase or decrease the value of the desired power factor. To confirm press the  button.
9

HARMONIC ANALYSIS PAGE

In the power factor controller it is possible to enable the calculation of the FFT harmonic analysis up to the 31st order of the
following measurements:
Absorbed reactive energy
IND / Exported reactive
energy CAP
Event
description
Software
Hardware
Parameters revision
level
Indicates the type of
maintenance to be
performed
31 / 86
rev9 jan19
Imported active energy IMP /
exported EXP
Key ► switches between
Total/Partial indications
Event time
stamp
Event number /
total
Plant / panel name
internal board temp.
Time remaining until the
next service
Date on which the
maintenance has been
performed

Publicité

Table des Matières
loading

Table des Matières