Rinnai Q Premier QP85N Instructions D'installation Et D'entretien page 75

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code
Description
contact for return sensor T2
open
Control unit error
Control unit error
Electrical leakage to ground.
No software present
Ribbon cable problem
Flue gas temperature to high
(adjustment parameter 84 -
default 212°F)
Fuse on controller PCB
defective
or
Cable transformer not
connected
Solution
Check the data in Error mode. Boiler data during error:
1 Error
= 37
2 Operational status = 00
3 Flow temp.
= xx*
4 Return temp.
= -22
5 kW burner
= 00**
6 % pomp
= xx*
* = variable values
**= x3415=BTU/hr
Check the wiring. check the wiring for the sensor
The wiring is OK but the error is repeated. Remove the plug from the fl ow
sensor as a result of which Error 32 occurs
Replace the sensor.
Software error control unit. Replace the control unit. The display will auto-
matically load the program into the new control unit.
Software error control unit. Replace the control unit. The display will auto-
matically load the program into the new control unit.
Moisture on controller PCB. Check if there is water leaking on or in the
boiler.
Stop water leak and replace controller
Control unit and display don't have a programm. There are a new display
and a new control unit installed at the same time. Exchange the parts and
the loading will start automatically and
Replace ribbon cable
Replace fl ue sensor or adjust parameter 84 to default
Replace fuse.
A 4A and 5A spare fuse can be found inside the Control Tower just above
the circuit board.
appears on the display.
75

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Q premier qp130n

Table des Matières