DISPLAY
LED STATUS
MESSAGE
green: <flashes>
PV voltage too
red: <off>
low
yellow: <off>
green: <flashes>
Synchronize
red: <off>
to AC
yellow: <off>
green: <on>
Varistor
red: <off>
warning
yellow: <flashes>
Please follow the instructions above before contacting your service technician!
9

Technical data

INPUT (DC)
Max. recommended PV
power
Nominal power
Voltage range
MPP range
Full power MPP range
Nominal current
Max. current
Stand-by power
STANDARDS / DIRECTIVES
Protection degree
Safety class
Configurable trip
parameters
Insulation monitoring
Overload behavior
Safety
Anti-islanding
protection
EMC
* The maximum AC power value indicates the power an inverter might be able to deliver. However, such a maximum AC
power may not necessarily be achieved.
** AC voltage and frequency range will be programmed according to the individual country requirements.
30
CAUSE
PV generator voltage bet-
ween 100 V and 150 V.
Check grid voltage and
grid frequency for grid
input mode.
Internal varistor at the DC
input is defective.
4000 W
P
3630 W
125 ... 540 V
150 ... 450 V
150 ... 450 V
13.3 A
24.0 A
< 0.2 W
IP65
1
Yes
Yes
Current limitation;
power limitation
EN60950-1; EN50178;
IEC62103; IEC62109-1 / -2
DIN VDE 0126-1-1; RD 1663;
RD 661; ENEL G.L. 2010; UTE
15712-1; Synergrid C10/11;
EN 50438; G83/1-1
EN61000-6-2; EN61000-6-3;
EN61000-3-2; EN61000-3-3

ELIMINATION

- Insufficient insolation.
- Check the PV cell voltage via the
display in the N menu.
- Normal function before input mode.
- Although you can, in theory, carry on
using the solar inverter, the varistors
should be replaced at the earliest oppor
tunity. This will involve returning the
device.
OUTPUT (AC)
Max. power *
Nominal power
Voltage range **
Nominal current
Max. current
Nominal frequency
Frequency range **
Power factor
Total harmonic
distortion (THD)
MECHANICAL DESIGN
Size (L x W x D)
Weight
Cooling
AC connector
DC connector pairs
Communication
interfaces
DC disconnector
Display
Operation and installation manual SOLIVIA 3.3 EU G3
3485 W
3300 W
184 ... 264 V
14.4 A
17.0 A
50 Hz
47.0 ... 52.0 Hz
> 0.99 @ nominal power
< 3 % @ nominal power
410 x 410 x 180 mm
21.5 kg
Convection
Wieland RST25i3S
3 Tyco Solarlok
2 Harting RJ45 / RS485
Integrated
LCD; 3 LEDs