Do Not Use For

The CM-E1 is NOT intended for use in industrial applications such as refineries, chemical plants, etc. The CM-E1 is NOT
intended for use in parking garages as the controller of exhaust systems. Do NOT use the CM-E1 for monitoring gases
other than Carbon Monoxide (CO). The CM-E1 is NOT designed to detect smoke, fire or any other gas. Do NOT mount the
unit in the garage. Do NOT mount the CM-E1 where the normal ambient temperature is below 40°F (4.4°C) or exceeds
100°F (37.8°C), or within 5 feet (1.5 meters) of a cooking or heating appliance. The Alarm Control Panel must be dedicated
to CO detection or have alarm devices that provide a distinctive alarm for carbon monoxide detection. Do not connect the
CM-E1 to Fire Alarm Circuits.
CM-E1 may not function effectively below 40°F (4.4°C) or above 100°F (37.8°C). Using the detector outside of this
temperature range may adversely affect product performance and result in sickness or death. (UL 2034)

General Description

The CM-E1 is for use with UL Listed Fire Alarm/Burglary Control Panels that have 12 to 24 VDC power and 12 to 24 VDC
alarm initiating circuits. The CM-E1 is intended for installation in buildings in non-hazardous locations such as residences,
retail stores, office buildings, and institutional buildings.
WARNING
7