Peak Shave
Settings –
Peak Shave
Rack Pwr
Thresh
Max Sup Pwr 1 KW
SOC Thresh
Settings -
REPO
Control
Settings
RS232
Baudrate
Settings –
Date
Date and
Time
Time
Settings
Discharge
Mode
Restore
Settings
Defaults
DISABLED
DISABLED,
ENABLED
6 KW
0 KW, 1 KW, 2
KW, 3 KW, 4 KW,
5 KW, 6 KW
0.5 KW, 1 KW,
1.5 KW, 2 KW,
2.5 KW, 3 KW
70%
30%, 40%, 50%,
60%, 70%, 80%,
90%
DISABLED
DISABLED,
ENABLED
9600
9600, 19200,
38400, 57600,
115200
00/00/00
00:00
DISABLED
DISABLED,
ENABLED
Enables or disables peak shave.
Rack power threshold. Amount of
power the rack must draw from the
AC6000 before peak shaving starts.
Maximum amount of power the
AC6000 supplies during peak shave.
Sets the battery state of charge
threshold where peak shaving is no
longer available.
Allow or Prevent Hardware REPO
shutdown.
Sets the baudrate of the RS232 bus.
Current date in DD/MM/YY format.
Current time in 24 hour format.
Runs the unit in fully discharging
mode to drain battery state of charge.
Restores the factory default settings.