SOC (%)
SOH (%)
C – Time (min)
D – Time (min)
Status Menu
Start
– Self Test
Result
Settings
Auto Start
Settings –
Auto
Output
Settings
Output Volt
Output
Frequency
Read-only
Read-only
Read-only
Read-only
NOT RUN
NOT RUN,
PASS, FAIL
ON
OFF, ON
ON
OFF, ON
208V
208V, 230V,
240V
60 Hz
50 Hz, 60 Hz
Battery state of charge.
Battery state of health.
Battery charge time to full in minutes.
Battery discharge time to empty in
minutes.
Start self-test mode.
Displays the results of the last
self-test. If self-test was not run since
the last power cycle, self-test displays
NOT RUN.
Enables the auto start feature.
Enables auto setting of output voltage
and frequency based on input voltage
and frequency.
Sets the output voltage of the
AC6000. This setting cannot be
changed when the Auto output is ON.
Sets the output frequency of the
AC6000. This setting cannot be
changed when the Auto option is ON.