6 Technical data of the
components
Illustr. 24 Summary of components
Note:
Further technical data and charts can be found in the
technical data sheets of the individual components
6.1 "Regumat M3-130" DN 20 heating circuit group
Illustr. 25 "Regumat M3-130" DN 20
32
Check valve
The check valve prevents a gravity circulation of the
heating water when the pump is switched off.
"Regusol L-130"
DN 20
(solar station)
"Regtronic RS-B"
(controller)
Storage cylinder
Illustr. 26 Check valve
The check valve is closed in operating position; pas-
"Regumaq XH"
sage is only possible in flow direction.
(fresh water station)
When putting the system into operation and during
maintenance work (filling and flushing), the check
valve must be opened.
Actuator
"Regumat M3-130"
The actuator NR230 of the three-way mixing valve
DN 20
(heating circuit group)
can be activated via the Oventrop system controller
"Regtronic RS-B" with three point output.
The angle of rotation is limited to 90°.
Having reached the limit stops, the actuator is swit-
ched off electrically and is without current. If the con-
trol system malfunctions, the actuator can be con-
verted to manual operation with the help of an
additional rotary knob.
Three point control:
Illustr. 27 Controller
Technical data:
Operating current
Absorbed power
Protective system
Torque
Operating time
Ambient temperature
Length of cable
Check valve
closed
WARNING
The electrical connection has to be carried out
according to the legal rules
NOTICE
The direction of rotation hot/cold depends on the
installation position of the three-way mixing valve
(supply/return).
Controller "Regtronic RS-B"
open
230 V 50 Hz
2.5 W
II (shockproof)
5 Nm
140 s
0 °C up to + 50 °C
2.2 m