Note:
When the circulation pump is switched off, a low
gravity circulation depending on the circulation pres-
sure is still possible within the heating system despite
the check valve as the latter is not tight sealing.
Dimensions
Illustr. 28 Dimensions "Regumat M3-130" DN 20
Technical data
Nominal size
Max. operating temperature 120 °C
Max. operating pressure
kvs value
Opening pressure
check valve
Connections
Pump length
Pressure loss chart
Flow chart "Regumat" DN20
DN 20
10 bar PN10
5.1
20 mbar
G1 male thread flat sealing
130 mm, G1 male thread
·
Flow rate V [l/h]
Pump characteristics
33