Figure 13 : Manual Furnace Controls

3.3

OPERATING SEQUENCE

This unit is designed to provide the required airflow in order
to match with any of four (4) different electronic heat
capacity, air conditioner or heat pump outdoor unit sizes
(see Tables 3 and 4 for CFM values).
Also, the blower motor is a true variable speed motor
designed to deliver constant CFM. Constant CFM is valid for
systems with total external static pressure between 0.1 and
0.7 inches water column.
Refer also to Table 1 for sequence of operation summary,
depending on thermostat inputs and types.
3.3.1.

Continuous fan

Thermostat closes circuit R to G.
Blower runs at continuous fan airflow.
3.3.2.
Cooling mode – single stage
If indoor temperature is above temperature set point and
humidity is below humidity set point, thermostat closes
circuits R to G, R to Y/Y2 and R to O.
NOTE: For single stage systems, do not use the Y1 terminal.
Furnace delivers single stage cooling airflow.
3.3.3.
Cooling mode – two stage
First stage (low) cooling: Thermostat closes circuits R to
G, R to O, and R to Y1.
Furnace delivers low stage cooling airflow.
Second stage (high) cooling: Thermostat closes circuits
R to G, R to O, R to Y1 and R to Y/Y2.
Furnace delivers high stage cooling airflow.
3.3.4.
Cooling mode – dehumidification
NOTE: Remove jumper « J1 » on board to activate this
function. (Refer to Figures 9 and 15)
If indoor temperature is above temperature set point and
humidity is above humidity set point, thermostat closes
circuits R to G, R to Y/Y2 and R to O and humidistat
opens circuit R to DH.
The furnace delivers airflow which is approximately 80%
of the nominal cooling airflow to increase the latent
capacity of the system.
3.3.5.
Electric heat heating mode – 1 stage
Thermostat closes circuit R to W1 or W2.
Furnace delivers the selected electric heat airflow and
maximum heating capacity is powered starting the
heating elements in sequence with a delay of 8 seconds
between each.
3.3.6.
Electric heat heating mode – 2 stage
NOTE: Remove jumper « J2 » on board to activate this
function. (Refer to Figures 9 and 15)
First stage heating: thermostat closes circuit R to W1.
Furnace delivers low stage heating airflow (50% of
nominal electric heating airflow) and approximately half
of the heating capacity is powered starting the heating
elements in sequence with a delay of 8 seconds
between each.
Second stage heating:thermostat closes circuit R to W2.
Furnace delivers high stage heating airflow (100% of
nominal electric heating airflow) and maximum heating
capacity is powered starting the heating elements in
sequence with a delay of 8 seconds between each.
3.3.7.
Heat pump heating mode – single stage
Thermostat closes circuits R to G and R to Y/Y2.
NOTE: For single stage systems, do not use the Y1 terminal.
Furnace delivers single stage heat pump heating
airflow.
3.3.8.
Heat pump heating mode – two stage
First stage (low) heating: Thermostat closes circuits R to
G and R to Y1.
Furnace delivers low stage heating airflow.
Second stage (high) heating: Thermostat closes R to G,
R to Y1 and R to Y/Y2.
Furnace delivers high stage heating airflow.
Electrical shock or unit damage hazard
Failure to carefully read and follow this WARNING could
result in equipment malfunction, property damage,
personal injury and/or death.
Disconnect power to unit before removing or replacing
connectors or servicing motor.
minutes after disconnecting power before handling.
3.4

AIRFLOW VERIFICATION

Verify the airflow by taking readings of the following points,
while the elements are in the heating mode:
Total amperage of all the heating elements;
Voltage at the furnace;
Supply air temperature. The point of the reading must
not be affected by radiant heat from the elements;
Return air temperature.
From these readings, one can arrive at an approximate
calculation of the average airflow. To do that, the following
formula should be used:
9