Table 1 : Sequence Of Operation - SUPREME SUP15-E230V1 Guide D'installation Et Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Mode
Continous Fan
(Fan switch ON)
Themostat calls for 1st stage Heat
Themostat calls for 2nd stage Heat
Continous Fan
(Fan switch ON)
Themostat calls for 1st stage Heat
Themostat calls for 2nd stage Heat
Themostat calls for Cooling
Themostat calls for Cooling &
Dehumidification
Continous Fan
(Fan switch ON)
Themostat calls for 1st stage Heat
Themostat calls for 2nd stage Heat
Themostat calls for 1st stage Cooling
Themostat calls for 2nd stage Cooling
Themostat calls for 2nd stage Cooling &
Dehumidification
Continous Fan
(Fan switch ON)
Themostat calls for Cooling
Themostat calls for Cooling &
Dehumidification
Themostat calls for 1st stage Heat
(Heat pump heating mode)
Themostat calls for 2nd stage Heat
(Electric heat) ∆
Continous fan
(Fan switch ON)
Themostat calls for 1st stage Cooling
Themostat calls for 2nd stage Cooling
Themostat calls for 2nd stage Cooling &
Dehumidification
Themostat calls for 1st stage Heat
(Heat pump heating mode)
Themostat calls for 2nd stage Heat
(Heat pump heating mode)
Themostat calls for 3rd stage Heat
(Electric Heat) ∆
* The 24 VAC is removed is remove from DH when there is a call for dehumidification
** Electric heat elements are controlled by relays with a delay sequence from Rectifier timer board on the relays
∆ The thermostat must provide Dual Fuel option or a Fossil Fuel kit must be used (electric heat elements & Heat pump must not run at the same time)
▼ Jumper J2 on the electronic board provide connection between W1 & W2. Remove it for 2 stage Electric Heat using a 2 stages thermostat.

Table 1 : Sequence of operation

Thermostat to Control
Control
Board 24 VAC
State
ON
G
OFF
ON
W1 ▼
OFF
ON
W1 & W2 ▼
OFF
Cooling 1 stage, with Electric Heat
ON
G
OFF
ON
W1 ▼
OFF
ON
W1 & W2 ▼
OFF
ON
Y/Y2 & G
OFF
ON
Y/Y2 & G & (DH)*
OFF
Cooling 2 stages, with Electric Heat
ON
G
OFF
ON
W1 ▼
OFF
ON
W1 & W2 ▼
OFF
ON
Y1 & G
OFF
ON
Y/Y2 & Y1 & G
OFF
ON
Y/Y2 & Y1 & G & (DH)*
OFF
Heat pump 1 stage, with Electric Heat
ON
G
OFF
ON
Y/Y2 & G & O
OFF
ON
Y/Y2 & G & O & (DH)*
OFF
ON
Y/Y2 & G
OFF
ON
W1 & W2 ▼
OFF
Heat pump 2 stages, with Electric Heat
ON
G
OFF
ON
Y1 & G & O
OFF
ON
Y/Y2 & Y1 & G & O
OFF
ON
Y/Y2 & Y1 & G & (DH)*
OFF
ON
Y1 & G
OFF
ON
Y1 & Y/Y2 & G
OFF
ON
W1 & W2
OFF
Electric Heat only
Fan ON at the selected continous fan CFM
Fan OFF
Fan ON at 50% of the selected Heat CFM, 1st stage of Heat ON**
1st stage of Heat OFF, Fan OFF
Fan ON at selected Heat CFM, 1st stage & 2nd stage of Heat ON**
1st stage & 2nd stage of Heat OFF, Fan OFF
Fan ON at the selected continous fan CFM
Fan OFF
Fan ON at 50% of the selected Heat CFM, 1st stage of Heat ON**
1st stage of Heat OFF, Fan OFF
Fan ON at selected Heat CFM, 1st stage & 2nd stage of Heat ON**
1st stage & 2nd stage of Heat OFF, Fan OFF
Compressor ON, Fan ON after delays at selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at 80% of the selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Fan ON at the selected continous fan CFM
Fan OFF
Fan ON at 50% of the selected Heat CFM, 1st stage of Heat ON**
1st stage of Heat OFF, Fan OFF
Fan ON at selected Heat CFM, 1st stage & 2nd stage of Heat ON**
1st stage & 2nd stage of Heat OFF, Fan OFF
Compressor ON, Fan ON after delays at 80% of the selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at 80% selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Fan ON at the selected continous fan CFM
Fan OFF
Compressor ON, Fan ON after delays at selected Cooling CFM
Compressor OFF, Fan OFF after selected Cooling delays
Compressor ON, Fan ON after delays at 80% of the selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at selected Heat Pump CFM
Compressor OFF, Fan OFF after selected Heat Pump delays
Fan ON at selected Heat CFM, 1st stage & 2nd stage of Heat ON**
1st stage & 2nd stage of Heat OFF, Fan OFF
Fan ON at the selected continous fan CFM
Fan OFF
Compressor ON, Fan ON after delays at 80% of the selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at 80% of the selected Cooling CFM
Compressor OFF, Fan OFF after selected cooling delays
Compressor ON, Fan ON after delays at 80% of the selected Heat Pump CFM
Compressor OFF, Fan OFF after selected Heat Pump delays
Compressor ON, Fan ON after delays at selected Heat Pump CFM
Compressor OFF, Fan OFF after selected Heat Pump delays
Fan ON at selected Heat CFM, 1st stage & 2nd stage of Heat ON**
1st stage & 2nd stage of Heat OFF, Fan OFF
12
Control Function