AC / HP SIZE
Adjustment
BLUE wire position
36
30
24
18
? In Cooling - Dehumidification mode (with Jumper J1 remove), with no 24 VAC input to DH, the CFMs are reduced by 15%.
? The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 only (Y/Y2 not powered)
? SYSTEM TYPE select to HP-EFF corresponds to 400 CFM/TONS - HP-COMF ORT c orresponds to 350 CFM/TONS
AC / HP SIZE
Selection
BLUE wire position
36
30
24
18
? CFM's when AC/HP CFM ADJUST at NOM position. CFM's 10% lower or higher if AC/HP CFM ADJUST at LO or HI position.
HEAT KW/CFM
adjustment
RED wire position
20
18
15
* Remove the Jumper J2 when a 2 stages thermostat is used
ON & OFF DELAY FOR COOLING AND HEAT PUMP HEATING MODE
ON / OFF DELAY
Adjustment
WHITE wire position
0 / 90
30 / 90
0 / 0
ENH
DELAY PROFIL E FOR ELECTRIC HEATING MODE
No adjustment
required
-
Table 3 : Electric furnace SUP, ECM ½ HP motor, air flow tables
COOLING OR HEAT PUMP HEATING MODE (WITH HP-EFF SELECTED ? )
24 VAC (R) input on G, Y/Y2 and O (for cooling)
CFM ?
A/C size
AC/HP CFM ADJUST
(T ONS)
BLACK wire position = (NOM)
3.0
1200
2.5
1000
2.0
1.5
24 VAC (R) input on G only
CF M ?
A/C size
CONTINUOUS FAN
(T ONS)
YELLOW wire position = (LO)
3.0
2.5
2.0
1.5
ELECTRIC HEATING MODE
24 VAC (R) input on W1 and/or W2 only
CFM
POWER
First stage
(Kw)
24 VAC on W1*
20
18
15
ON-Delay
OFF-Delay
Time
% CFM - Time
0 sec.
100% - 90 sec.
30 sec.
100% - 90 sec.
0 sec.
0 sec.
30 sec.
70 % - 150 sec.
ON-Delay
OFF-Delay
Time
% CFM - Time
0 sec.
50% - 60 sec.
AC/HP CFM ADJUST
BLACK wire position = (LO)
800
600
CONTINUOUS FAN
CONTINUOUS FAN
YELLOW wire position = (MED)
600
500
400
300
24 VAC on W1 and/or W2*
500
450
400
18
CFM ?
AC/HP CFM ADJUST
BLACK wire position = (HI)
1080
900
720
540
CFM ?
YELLOW wire position = (HI)
960
800
640
480
CFM
Second stage
1000
900
800
CFM ?
1320
1100
880
660
CFM ?
CONTINUOUS FAN
1200
1000
800
600