Installation
Supplies Required
• (3) 3/8" floor anchors and bolts
• Teflon tape and pipe sealant
• Piping to 1-1/4" NPT water supply inlet and 1-1/4"
NPT drain outlet on unit
• Adequate supply pipe supports
• Minimum 4" (102mm) drain to accommodate 30
gallons (115 liters) per minute discharge for shower
waste
• OPTIONAL: sign-mounting hardware
Local codes may require the installation of a backflow
prevention valve to complete proper installation.
Compliance with local codes is the responsibility of
the installer. Valve must be tested annually to verify
that it is functioning properly. Backflow prevention
valves are not included with the fixture and may be
supplied by the contractor or purchased from Bradley
Corporation.
Secure base to floor
1. Install three suitable anchors (supplied by installer)
for 3/8" bolts in the floor.
2. Bolt the base to the floor anchors using 3/8" bolts
(supplied by installer).
Assemble components
1. Assemble the remaining unit components as shown
on page 4.
2. Apply pipe sealant (by installer) to all male-threaded
pipe joints.
3. Use the rubber grip pad provided or a strap wrench
around pipes when tightening to prevent marring.
Place the grip pad on the pipe, then put the wrench
over the grip pad and turn the pipe with the wrench.
4. Bottom edge of the showerhead should be 7'-2"
(2180mm) from floor.
Connect water supply
NOTICE! Do not rely on Bradley's Combination Unit to
support supply piping.
1. Connect water supply piping to 1-1/4" NPT inlet on
unit (piping by installer). Provide adequate supports
(by installer) for supply pipe using pipe hangers or
other means.
2. Connect drain piping to 1-1/4" NPT drain outlet on
unit (piping by installer).
3. Hang the safety sign from the unit with the curtain
hooks provided (or mount it to the wall using sign-
mounting hardware by installer).
Bradley • 215-163DC Rev. X; ECN 17-05-039
25-3/8"
(645mm)
4-1/2"
(114mm)
Ø 3.1"
(610mm)
(78.7mm)
9"
(229mm)
7'-2"
(2180mm)
to Floor
Ø 10-3/4"
(273mm)
10-1/2"
(267mm)
Top View From Bowl
All dimensions assume standard thread
engagement. Variations in manufacturing
allow for +/- 1/8" (3mm) per threaded joint.
To find the tolerance of a dimension, add
the number of thread joints in between a
dimension and multiply it by 1/8" (3mm).
7/18/2017
S19-310DC
24"
(1676mm)
to Floor
5-1/2"
(140mm)
36-3/8"
(924mm)
6"
(152mm)
9-1/2"
(241mm)
Ø 9" (229mm) Flange
with (3) Ø 3/8" (10mm)
Holes on Ø 8" (203mm)
Bolt Circle
66"
3