ECA 150 ipro H, ECA 150 ipro KH
The unit is fully accessible and ventilates at
performance level 1 or 2 depending on the
automatic humidity process. When humidity
is low it switches off completely. Alternatively,
the unit can be switched on and off with a
switch provided by the customer (which takes
priority over the automatic humidity process).
It is then operated with the set start delay and
overrun time as defined by one of 4 operating
programs (Comfort, Demand, Save or Power
Chapter 7.2.1). The sequence of
performance levels is determined in the
operating program. For function of humidity
control Chapter 2.6.
ECA 150 ipro RC, ECA 150 ipro KRC,
ECA 150 ipro RCH, ECA 150 ipro KRCH
RLS RC programs
for ECA 150 ipro
RC/KRC/RCH/KRCH
Master
Program P1
Slave(s)
Master
Program P2
Slave(s)
Performance level 1 = 200 m³/h
Performance level 2 = 250 m³/h
(Values for free outlet)
ECA 150 ipro RC, ECA 150 ipro KRC
The unit is switched on/off either at the room
air control RLS RC, with the radio switch
DS RC, or with a window radio contact to
be supplied by the customer.
For the function of wireless components,
see description of Maico Smart in
Chapter 2.7.
System
System
level 0
level 1
off
Perform. level 1
off
off
off
Perform. level 2
off
off
ECA 150 ipro
ECA 150 ipro
B,
The unit is barrier-free and offers air
extraction through movement automatics
according to one of the four operating
programs ( Chapter 7.2.1). If no movement
is identified, it switches off completely after
the set overrun time.
Alternatively, the unit can be switched on and
off with a switch provided by the customer
(which takes priority over the motion sensor
system). It is then operated with the set
overrun time (without a start delay) as defined
by one of 4 operating programs (Comfort,
Demand, Save or Power Chapter 7.2.1).
The sequence of performance levels is
determined in the operating program.
System
level 2
Perform. level 1
Perform. level 1
Perform. level 1
Perform. level 1
ECA 150 ipro RCH, ECA 150 ipro KRCH
The unit is barrier-free. Air extraction is
executed according to automatic humidity
operation. If there is little humidity, the unit
switches off completely.
For manual operation via radio component,
ECA 150 ipro RC, ECA 150 ipro KRC.
The automatic humidity process takes priority
over manual operation.
10. Maintenance
The unit is maintenance-free.
9. Operation │ uk
KB
System
level 3
Perform. level 2
Perform. level 1
Perform. level 2
Perform. level 2
29