Select the desired program, Comfort,
Demand, Save or Power, with jumpers
J4 and J5 ( fig. H).
Comfort program (factory setting)
Performance level 1 while room is being
used, performance level 2 during overrun
time. J4 and J5 bridged.
Demand program
Performance level 2 while room is being
used, performance level 1 during overrun
time. J4 and J5 open.
7. Installation – Electrical connection, operating programs │ uk
Save program
Performance level 1 during operation and
overrun. J4 open, J5 bridged.
Power program
Performance level 2 during operation and
overrun. J4 bridged, J5 open.
7.2.2 Sensor and covers
Danger of short circuits and
NOTICE
damage to unit. Humidity will
penetrate if electronics cover
is not fitted correctly.
Press electronics cover firmly
onto housing such that it is
sealed and flush all the way
around. Be careful not to press
setting buttons [11] and [12].
1. Press electronics cover on to 3 locking
tabs at housing recesses I, II and III
( fig. G) until it locks into place. Also
press the electronics cover firmly on to the
housing at the two points indicated by the
word PRESS.