How to Install Your
Hardwired Charger

(EVR30-B1C, EVR40-B2C, and EVR30-R2C)

WARNING: TO AVOID FIRE, SHOCK OR DEATH, TURN OFF POWER at the circuit
breaker or fuse and test that the power is off before wiring or before working inside the
equipment or removing any component. Do not remove circuit protective devices or any
other component until the power is turned OFF!
IMPORTANT SAFETY INSTRUCTIONS
The AC Charger shall be installed only by a licensed contractor, and/or a licensed
electrician in accordance with all applicable state, local and national electrical codes and
standards. Before installing the AC Charger, review this manual carefully and consult
with a licensed contractor, licensed electrician and trained installation expert to ensure
compliance with local building practices, climate conditions, safety standards, and
state and local codes. Use appropriate protection when connecting to the main power
distribution cable.
GROUNDING INSTRUCTIONS
The AC Charger must be connected to a grounded, metal, permanent wiring system;
or an equipment grounding conductor must be run with the circuit conductors and
connected to the equipment grounding terminal on the product.
WIRING DIAGRAMS
240V Single Phase
WARNING: The two phases used must each measure 120V to Ground. Earth
ground must be connected to neutral at only one point, usually at the breaker panel.
120V
NEUTRAL
(NOT USED)
120V
7
L1
240V
L2
GND