The basic elements of 43LEC000 Logger are:
1. LCD display for listing the events.
2. Buttons for operation and settings:
Up arrow
Viewing the menus; setting the date, time and language.
Down arrow
Viewing the menus; setting the date, time and language.
Cancel
Rejecting the entered data; Exit from menu.
Enter
Enter in a menu; Confirmation of the entered data according the current status.
3. LED indicators for presence of power supply from the control panel and communication status
(transmitting and receiving data form the control panel – fast blinking in orange).
4. LED indicator for displaying of lost communication with the control panel – the LED blinks in yellow in
case of lost connection with the panel.
5. Terminals for connecting to ERACLE16 control panel:
+ / - 24V
- Power supply from the control panel
+ / - Tx
- Transmitting data to the control panel
+ / - Rx
- Receiving data from the control panel
6. Jumper for storing the set time and date of the module.
7. Mounting holes.
5. Mounting and Connecting
ATTENTION: Switch OFF the main and back-up power supply of ERACLE16 control panel before
mounting and connecting the 43LEC000 Logger module!
IMPORTANT NOTE: For correct operation of 43LEC000 module, the fire alarm panel ERACLE16
must be programmed to operate in MASTER operation mode – a jumper is set on the MASTER
terminals on the main board.
Picture 1
Installation steps of 43LEC000 Logger into ERACLE16:
1. Open the front cover of ERACLE16 and switch off the main power
supply and the battery.
2.
Mount the Logger PCB as shown on Picture 1 - on the internal side
of the cover, over the printer opening, with the LCD display on top.
3. Fix the 43LEC000 Logger PCB to the cover with the supplied in the
kit mounting screws.
4. Connect the module to ERACLE16 Control Panel as shown on
Picture 2(a), using the supplied connection cable in the set.
5. Set a jumper for storing the time and date of the events – set a
jumper on position 6 as shown at item 4.
Picture 2 (a) - Connection diagram of
43LEC000 Logger to ERACLE16
43LEC000 – Tecnical Manual
3