Technical Specifications - Festo VIFB5 Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 27
VIFB5 - 03/05
5

Technical specifications

Type
Protection class (as per DIN 40050)
Ambient temperature
Storage temperature
Pin 1 - Operating voltage connection
for electronic components/inputs
• Rated value
(protected against incorrect polarity)
• Tolerance
• Permitted current consumption
Pin 2 - Operating voltage connection
for outputs/valves
• Rated value
(protected against incorrect polarity)
• Tolerance
• Permitted current consumption
Fuse for supply to inputs/sensors
Electromagnetic compatibility
• Interference emitted
• Immunity against interference
1)
The component is intended for industrial use.
18
VIFB5-..-
IP 65 (completely mounted)
o
o
- 5
... + 50
C
o
o
- 20
... + 60
C
DC 24 V
± 25 % (DC 18 V...30 V)
max. 2,2 A
DC 24 V
± 10 % (DC 21,6 V...26,4 V)
max. 10 A
2 A slow blowing (internal)
Tested as per DIN EN 61000-6-4
1)
(industry)
Tested as per DIN EN 61000-6-2
(industry)
0503a