3-Position-Bbpr (Gfs) Models - Burkert 3004 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour 3004:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3-POSITION-BBPR (GFS) : description
The GFS version includes BBPR battery backup and 3-position versions.
BBPR battery backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close (default) or
open.
GF3 option allow actuator to be drive and stop in 3 positions. These 3 positions could be between 0° to 180°.In standard actuators
are setting in our workshop at 0° 90° 180° that's fit with standard 3 ways ball valve. Others positions still available but customer have
to price on the order witch position is request.
Par défaut, la configuration en sortie d'usine est "normalement fermé"
Actuator voltage
Battery voltage
Battery capacity
Charging current
battery charge maximum duration
Electric connection
The caps placed on M20x1.5 openings (appendix p.44 mark 16) must be replaced by ATEX and IP68 metallic certified cable
glands. The unused threaded opening must be closed with ATEX and IP68 certified caps.
Power supply and control wiring
Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.
Unscrew the left cable gland and insert the cable.
Remove 25mm of the cable sheath and strip each wire by 8mm.
Connect the wires to the terminal strip in accordance with the diagram p. 55.
Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Feedback wiring and contacts state
Unscrew the right cable gland and insert the cable.
Remove 25mm of the cable sheath and strip each wire by 8mm.
Connect the wires to the terminal strip in accordance with the diagram p. 55.
Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
The reinforced insulation from the motor control, allows voltages up to 250 V AC/DC.
Our 3-position actuators have 3 auxiliary switches
FC1 (white cam - 5th): open position feedback - NO
FC2 (black cam - 6th) : closed position feedback - NO
FC3 (beige cam - 7th) : intermediate position feedback - NF
To adjust the position of the auxiliary contacts, make rotate the 3 superior cams by using the appropriate wrench.
The actuator is pre-set in our factory. Do not touch the two lower cams in order to avoid any malfunctioning or even damage
to the actuator.
The battery charge cycle is automatically managed by the electronic card since the first power up. A CTN in the battery pack
and a fuse on the electronic card are present to ensure safety in the event of a short circuit or excessively high temperature
54
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
24 V DC
Charging status feedback relay (65/66)
600 mAh
Failure feedback relay (D3/D4)
180 mA
Temperature
3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 07 ATEX 6078X / LCIE 22.0001X
Ambient temperature: -10 °C to +40 °C
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
Terminals
6 & 9
4 & 8
Closed
Open
inter
Open
Open
180°
Open
Closed
3004 • Rev. 2109/06 • 00806090
EN
F4 & F9
Closed
Open
Fermé

Publicité

Table des Matières
loading

Table des Matières