3-Position (Gf3) Model - Burkert 3004 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour 3004:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
BBPR (GS6) : electric connection
The caps placed on M20x1.5 openings (appendix p.44 mark 16) must be replaced by ATEX and IP68 metallic certified
cable glands. The unused threaded opening must be closed with ATEX and IP68 certified caps.
Power supply and control wiring
Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.
Unscrew the left cable gland and insert the cable.
Remove 25mm of the cable sheath and strip each wire by 8mm.
Connect the wires to the terminal strip in accordance with the diagram p. 50.
Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Position feedback wiring
Unscrew the right cable gland and insert the cable.
Remove 25mm of the cable sheath and strip each wire by 8mm.
Connect the wires to the terminal strip in accordance with the diagram p. 50.
Tighten the cable gland ATEX & IP68 (Ensure that it's well mounted to guaranty the proofness).
The reinforced insulation from the motor control, allows voltages up to 250 V AC/DC.
Our actuators are equipped with two simple limit switch contacts normally set either in open position, either in closed position.
As per factory setting, the white cam is used to detect the open position (FC1) and the black cam is used to detect the closed
position (FC2).
The actuator is pre-set in our factory. Do not touch the two lower cams in order to avoid any malfunctioning or even damage
to the actuator.
The battery charge cycle is automatically managed by the electronic card since the first power up. A CTN in the battery pack
and a fuse on the electronic card are present to ensure safety in the event of a short circuit or excessively high temperature
in the actuator .
Setting of end limit switches
To adjust the position of the auxiliary contacts, make rotate the two superior cams by using the appropriate wrench.
Thanks to remot3XApp (via Bluetooth
of power failure.
it's also possible to access to actuator parameters in real time, to schedule weekly tasks and to control it locally.
3004 • Rev. 2109/06 • 00806090
®
connection), it's possible to set the Initial security position that the actuator will reach in case
49

Publicité

Table des Matières
loading

Table des Matières